101
F29
EEROM error
Inconsistency is detected once without
verify ACK after writing to EEPROM.
××
1. Replace the water heat exchange
control board.
1—
F30
Extended IC error
When the extended IC is abnormal.
××
1. Replace the water heat exchange
control board.
1123
F32
Flow sensor error
Heating
×
Hot water
O
O
1. Check the connection of flow
sensor.
2. Check the flow rate detected by flow
sensor and actual flow.
1124
F33
Flowing quantity error
1)Detected by TC sensor
TC 68°C is detected in the heating or
hot water supply heat pump operation
(except for defrosting).
Heating
×
Hot water
O
×
No or little water flow
Defect of the flow sensor
4
124
2)Detected by flowing quantity
When the stopped built-in circulation
pump starts its operation, the flow
sensor status is detecting “water flow”.
Defect of the flow sensor
Misconnection of flow sensor and
low pressure sensor
Check the water flow from the
external pump.
2
L02
Combination error
Model name of the outdoor unit is
different.
××
1. Check the model name of the
outdoor unit.
1125
L03
Duplicate main Hydro unit during
Group control
There are more than one header
units in group.
××
1. Check Hydro Unit addresses.
(DN_14)
2. Check for any change made to
remote control connection (group /
individual) since Hydro address
setting.
1—
L07
Communication error
Individual hydro units have a group line.
××
1. Replace the water heat exchange
control board.
1125
L08
Hydro Unit group / Address unset
Address setting has not been performed
for Hydro units.
××
1. Check Hydro Unit addresses.
Note:
This code is displayed when power is
turned on for the first time after
installation.
1—
L09
Communication error
The capability code for the hydro unit
has not been set.
××
1. Check the setting of the DN_11
capability specifications.
601 Hydro = 0010
1101 Hydro = 0015
1125
L16
Setting error
When ZONE1 has not been set, while
ZONE2 has been set.
××
1. Check the DN_6B9, 6BA and set
correctly.
1125
L22
0-10 V Setting error
DN680 settings in group control are not
the same for all units.
××
1. Check the 0-10 V setting for all units.
(DN_680)
1125
P31
Slave Hydro unit error which occurs
when error occurs in master Hydro
unit
×
O
1. Check the remote controller
connection.
2. Defect in the remote controller.
3. Set the address No. of DN_12 ~ 14
correctly for each Hydro unit.
1—
Check
code
Diagnostic functional operation
Determination and action
Number of
abnormalities
for
confirmation
Detailed
item
Operational cause
Backup
operation
Automatic
reset