61
7-2.
Operation Mode
and Control
Method
7) Boiler control
The boiler assists the hot water supply operation and heating operation according to the boiler’s position.
7-1) Boiler setting
Connect its connection cable to CN22 port on the PC board of the hydro unit.
DN_6B0 = “0/1” switches “Not using boiler (Default) / Using boiler”.
Set the DN_6B0 to “1” when using the boiler.
The temperature switching the boiler and heat pump: DN_23 = -10°C (Default) See the next item.
The boiler output becomes effective when the outside air temperature is -10°C or less.
Boiler position setting: DN_6B1 = “0/1” must be switched in accordance with the boiler position from the 3-way
valve; before the 3-way valve / after the 3-way valve and in the heating side (Default).
When the DN_6B1 is set to “1”, the boiler runs in the hot water supply operations or heating operation. The action
of the 3-way valve depends on heat pump’s action and the boiler follows their action.
When the DN_6B1 is set to “0”, the boiler runs in heating operation. Also, the boiler runs when the heat pump is
running for heating while heating and supplying hot water simultaneously.
Priority setting between the boiler and hydro unit: DN_3E = “0/1” switches the running priority; hydro unit (Default)
/boiler.
When DN_3E is set to “0” (Default), the hydro unit has priority, the boiler stops as inlet water temperature reaches
the hydro unit’s temperature setting.
When DN_3E is set to “1”, the boiler continues to run even after inlet water temperature reaches the hydro unit’s
temperature setting. (The setting of DN_3E is effective during the HP+Boiler operation.)
Coordination setting of the boiler and heat pump: when DN_5B = “0”, the boiler and heat pump runs simultaneously.
When DN_5B = “1”, only the boiler runs, pump ON. (However, if the external air temperature becomes the boiler-
HP switching temperature or more within 60 minutes)
When DN_5B = “2”, the heater runs. (the heater may run instead for up to 60 minutes.)
When DN_5B = “3”, only the boiler runs. (Pump OFF: Default)
DN_6B5 should be “0 (Default)”
<Installation example>
DN_6B1 = “0” (The boiler is placed after the 3-way valve and in the heating side.)
DN_6B1 = “1” (The boiler is placed before the 3-way valve.)
Item Operation flow and applicable data, etc.
Boiler
Outdoor
unit
Hydro unit
Buffer tank
Radiator
TO <= -10* -10* < TO
HEATING Boiler + HP** HP
HOT WATER HP HP
HEATING & HOT
WATER
Boiler for heating
HP for hot water
or heating
HP
COOLING HP (TO 10)
COOLING & HOT
WATER
HP for cooling
Heater for hot
water***
HP for cooling
Heater for hot water***
* Boiler & HP switching temp setting DN_23 = -10
** Boiler control / functionality setting DN_5B = 0 (HP+Boiler)
*** Hot water & cooling priority setting (DN_0F = “1” hot water
priority is necessary.)
Boiler
Buffer tank
Radiator
Outdoor
unit
Hydro unit
TO <= -10* -10* < TO
HEATING Boiler + HP** HP
HOT WATER Boiler + HP** HP
HEATING & HOT
WATER
Boiler + HP** HP
COOLING HP (TO 10)
COOLING & HOT
WATER
HP for cooling
Heater for hot
water***
HP for cooling
Heater for hot water***
* Boiler & HP switching temp setting DN_23 = -10
** Boiler control / functionality setting DN_5B = 0 (HP+Boiler)
*** Hot water & cooling priority setting (DN_0F = “1” hot water
priority is necessary)