81
7-3.
Hydro Unit Control
11) Connection to a Smart Grid network (SG ready)
The operating mode is controlled through volt free contacts incorporated into the energy meter.
Connect its connection cable to CN21 port on the PC board of the hydro unit.
Optional inputs to Hydro Unit
This unit has eight input ports. 2 ports of them are selectable by DN. Table2 shows the selectable input functions and
default settings.
Non-voltage contacts
11-1)The Settings
I/P7 & I/P8: Connection to a Smart Grid network (SG Ready)
Non-voltage contacts
The operating mode is controlled through volt free contacts incorporated into the energy meter.
Setting: DN_B6 = “4”
DN_6CE = “0”: HP and backup heaters ON when “System Forced ON” mode
DN_6CE = “1”: HP operation only when “System Forced ON” mode
DN_AC = “0~10”: Setting to increase the space heating set point temperature when “System Forced ON” mode
11-2)The operation mode and control summary
0: The terminals are opened , 1: The terminals are closed
Item Operation flow and applicable data, etc.
MCC-1755
I/P 4
common
line
CN21
1
2
3
4
5
6
7
8
9
10
Hydro Unit sub PCB
common
line
I/P 3
I/P 2
I/P 1
I/P 8
I/P 7
I/P 6
I/P 5
Locally procured
Input items (Default setting)
I/P 1 Room thermostat input for heating
I/P 2 Room thermostat input for cooling
I/P 3 Hot water tank thermostat input
I/P 4 Heating/cooling mode switching input
I/P 5 Heating/cooling operation ON/OFF
I/P 6 Hot water operation ON/OFF
I/P 7 (DN_B6) 0: Emergency shutdown input
I/P 8 (DN_B6) 0: None
I/P 7 I/P 8 Mode Control summary
0 0 Restricted Operation
Normal operation but with maximum compressor frequency limited to
certain value (night time operation)
Back up heater control is active
Boiler output control active
1 0 System OFF
The heat pump and electric heaters are FORCED OFF for a maximum of 2
hours during this period.
The space heating and DHW set points will continue to be displayed on the
remote controller.
System safety controls (e.g. freeze protection) will remain active.
Boiler output control will remain active.
0 1 Normal Operation
This signal is not a START signal – only a recommendation to start
The heat pump and electric heaters are available to operate under normal
control if there is a heating or DHW demand
There is no restriction on the compressor frequency – the compressor can
operate at maximum frequency if requested by the outdoor unit control
software
1 1 System Forced ON
During this period the system is FORCED ON to allow the heat pump and
back up heater to operate
The space heating set point temperature is increased during this period.
The temperature increase can be adjusted using DN_AC.
If there is a DHW demand during this FORCED ON period then the DHW
set point is increased to the set point used for the DHW boost function
The hydro unit back up heaters will continue to operate with a modified
control where by the ON/OFF heater delay will be removed
All other controls will remain active (e.g. DN_22, DN_1A etc.)
* Backup heater is not energized during boiler output is ON.