Auto-Curve temperature shift
• This function is available only for the header remote controller.
• The set temperature can be shifted in the range of ±5K of the current setting.
1 Press the [ ] / [ ] button to select “Auto mode” on the MENU
screen.
2 Press the [ ] button for 4 seconds or longer to enter the setting mode. The DN code setting
screen appears.
DN_27: Shifted temperature (Range: -5 ~ +5, Default: 0)
3 Press the [ ] button to select Data value, then press the [ ] / [ ] button to adjust the
temperature between -5K to +5 K.
4 Press the [ ] button. The set temperature is registered.