5-2. RAS-10GKP-ES2 / RAS-10GA-ES2
Note :
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
Ambient temp.
conditions DB/WB
C)
Indoor Outdoor
Standard 0.95 10.5 High 27/19 35/24
Cooling Overload 1.12 16.0 High 32/23 43/26
Low temperature 0.71 2.0 Low 21/15 21/15
Fan speed
(indoor)
50Hz
Indoor unit
Cross flow fan
Cooling
Cooling
Compressor
Heat exchanger
Propeller fan
Outdoor unit
PA108X1C-4FZDN
Cooling
Mark( )means check points of Gas Leak.
O.D.:9.52mm O.D.:6.35mm
Cooling
Packed valve
(9.52)
Packed valve
(6.35)
0.39m
(Connecting pipe)
9.52
0.49m
(Connecting pipe)
6.35
T1
P
Refrigerant
R410A : 0.72 kg.
Heat exchanger
Capillary tube
1.5x1100l
Standard
pressure
P
(MPaG)
Surface temp. of heat
exchanger interchanging
pipe
T1
(°C)
FILE NO. SVM-06039
RAS-10GKP-AS2 / RAS-10GA-AS2