7. REFRIGERANT CYCLE DIAGRAM
7-1. Refrigerant Cycle Diagram
FILE NO. SVM-11015-1
NOTE :
The maximum pipe length of this air conditioner is 25 m. When the pipe length exceeds 15m, the additional
Max. : 25m
Deoxidized copper pipe
Outer dia. : 9.52mm (10,13)
: 12.7mm (16)
NOTE :
Gas leak check position
Refrigerant flow (Cooling)
Refrigerant flow (Heating)
INDOOR UNIT
T1
TO
Temp. measurement
Indoor heat
exchanger
Cross flow fan
Deoxidized copper pipe
Outer dia. : 6.35mm
Thickness : 0.8mm
Sectional shape
of heat insulator
Allowable height
difference : 10m
Allowable pipe length
P
Pressure measurement
Gauge attaching port
Vacuum pump connecting port
Muffler
Pulse Modulating
valve at liquid side
Ø1.2 x 80
Ø1.2 x 80
TD
4-way valve
Compressor
DA111A1F-20F1
TS
T2
Outdoor heat
exchanger
Split capillary
Temp. measurement
Propeller fan
Refrigerant amount : 1.05kg
OUTDOOR UNIT
Muffler
Muffler
TE
TC
TA
Min. : 2m
Chargeless : 15m
Charge : 20g/m
(16 to 25m)
Thickness : 0.8mm
charging of refrigerant, 20g per 1m for the part of pipe exceeded 15m is required. (Max. 200g)
Strainer
Tcj