FILE NO. SVM-11015
7-2. O
p
eration Data
<Coolin
g
>
Tempeature Model name Standard Heat exchanger Indoor Outdoor Compressor
condition(°C) RAS- pressure pipe temp. fan mode fan mode revolution
Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)
27/19 35/- 10SKVP2-E 0.9 to 1.1 12 to 14 40 to 42 High High 37
13SKVP2-E 0.8 to 1.0 8 to 10 41 to 43 High High 58
16SKVP2-E 0.7 to 0.9 7 to 9 42 to 44 High High 83
<Heating>
Tempeature Model name Standard Heat exchanger Indoor Outdoor Compressor
condition(°C) RAS- pressure pipe temp. fan mode fan mode revolution
Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)
20/- 7/6 10SKVP2-E 2.5 to 2.7 36 to 38 2 to 3 High High 49
13SKVP2-E 2.7 to 2.9 40 to 42 2 to 3 High High 65
16SKVP2-E 2.9 to 3.1 49 to 51 1 to 2 High High 83
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchaner path U bent.
(Thermistor themometer)
2. Connecting piping condition : 5 m