102
11-9-5. Checking Method for Each Part
No.
1
Part name
Electrolytic capacitor
(For boost, smoothing)
Checking procedure
1. Turn OFF the power supply breaker.
2. Discharge all two capacitors completely.
3. Check that safety valve at the bottom of capacitor is not broken.
4. Check that vessel is not swollen or exploded.
5. Check that electrolytic liquid does not blow off.
6. Check that the normal charging characteristics are shown in continuity test by
the tester.
Case that product is good
Pointer swings once, and returns
slowly. When performing test
once again under another
polarity, the pointer should return.
C09, C10 760µF
Resistance value
in good product
Tester rod
+
~
2
~
3
~
2
~
3
4
~~
~
+ ~
1
123
(DB01,DB02)
4
4
23
+
1
+
10 to 20 when the multimeter probe
is reversed
2
Diode block
1. Turn OFF the power supply breaker.
2. Completely discharge the two electrolytic capacitors.
3. Remove the diode block from the PCB (which is soldered in place).
4. Use a multimeter with a pointer to test the continuity, and check that the
diode block has the proper rectification characteristics.
FILE NO. SVM-14017

Table of Contents