7-2. Operation Data
FILE NO. SVM-12056
<Cooling>
Standard Heat exchanger Indoor Outdoor Compressor
pressure pipe temp. fan mode fan mode revolution
Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)
27/19 35/24 18N3KV2-E 0.9 to 1.1 11 to 13 40 to 42 67
B22N3KV2-E 0.9 to 1.1 11 to 13 41 to 43 77
<Heating>
Tempeature Standard Heat exchanger Indoor Outdoor Compressor
condition(°C) pressure pipe temp. fan mode fan mode revolution
Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)
20/15 7/6 18N3KV2-E 2.5 to 2.6 40 to 42 1 to 3 79
B22N3KV2-E 2.6 to 2.8 42 to 44 0 to 2 84
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchaner path U bent.
(Thermistor themometer)
2. Connecting piping condition : 7.5 m
Tempeature
condition(°C)
Model name
RAS-
Model name
RAS-
HighHigh
High High
– 22 –