- 16 -
FILE NO. SVM-09036
5-4. RAS-24SKHP-ES / RAS-24S2AH-ES
Heat exchanger
Indoor unit
Cross flow fan
Cooling
Heating
4-way valve
Heating
Cooling
Compressor
Accumulator
Heat exchanger
Propeller fan
Outdoor unit
Capillary tube
Æ2.0 x 900
Capillary tube
Æ2.0 x 700
PA270X3CS-4MU2
Cooling
Heating
Mark ( ) means check points of Gas Leak.
O.D.:12.7 mm O.D.:6.35 mm
Cooling
Heating
Packed valve
(Æ12.7)
Packed valve
(Æ6.35)
0.39 m
(Connecting pipe)
0.49 m
(Connecting pipe)
T1
P
Refrigerant
R410A 1.62 kg.
Æ12.7
Æ6.35
Ambient temp.
conditions DB/WB
C)
Indoor Outdoor
Standard 2.86 45.6 High 20/15 7/6
Heating Overload*1 3.54 ~ 3.91 53.6 ~ 57.6 Low 27/- 24/18
Low temperature 2.19 33.9 High 20/
Standard 0.84 10.0 High 27/19 35/24
Cooling Overload 1.12 16.1 High 32/23 43/26
Low temperature 0.74 2.3 Low 21/15 21/15
Standard
pressure
P
(MPaG)
Surface temp. of heat
exchanger interchanging
pipe
T1
(°C)
Fan speed
(indoor)
50Hz
Note
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
*1 During heating overload operation, a value for the high temperature limit control operation is included.
l
l
-
-10/-10
·
·
Discharge Muffler
25x160L