– 5 –
FILE NO. SVM-05016
Note : 1
• Capacity is based on the following temperature conditions.
Note : 2
• Charge refrigerant according to the table below.
RAS-24NKHD-E4 / RAS-24UAH-E4 RAS-18NKHD-E4 / RAS-18UAH-E4
RAS-24NKD-E4 / RAS-24UA-E4 RAS-18NKD-E4 / RAS-18UA-E4
Refrigerant RAS-24NKDX4 / RAS-24UAX4 RAS-18NKDX4 / RAS-18UAX4
RAS-24NKD-AR4 / RAS-24UA-AR4 RAS-18NKD-AR4 / RAS-18
UA-AR4
RAS-24NKDX4-T / RAS-24UAX3-T1 RAS-18NKDX4-T2 / RAS-18UAX4-T2
1 No need to charge
15 m or less 15 m or less
extra refrigerant
2 Need to charge
Over 15 m up to 25 m (30 g/m) Over 15 m up to 20 m (20 g/m)
extra refrigerant
Temperature
Condition
JIS B8615-1
Cooling Heating
Indoor unit inlet air temperature
(DB) 27°C 20°C
(WB) 19°C 15°C
Outdoor unit inlet air temperature
(DB) 35°C 7°C
(WB) 24°C 6°C