Check codes and parts to be checked
Indication
Judging
device
Parts to be checked / error description
conditioner
E01
No header remote
controller
Remote
controller
Incorrect remote controller setting --- The header remote controller has not
been set (including two remote controllers).
*
Remote controller
communication error
No signal can be received from the indoor unit.
E02
Remote controller
transmission error
Indoor/outdoor connecting wires, indoor P.C. board, remote controller ---No
signal can be sent to the indoor unit.
*
E03
controller regular
Indoor
Remote controller, network adapter, indoor P.C. board --- No data is received
from the remote controller or network adapter.
Auto-reset
E04
unit serial
Indoor
Indoor/outdoor connecting wires, indoor P.C. board, outdoor P.C. board ---
Serial communication error between indoor unit and outdoor unit
Auto-reset
IPDU-CDB
communication error
E08
Duplicated indoor
addresses
Indoor
Indoor address setting error --- The same address as the self-address was
Auto-reset
E09
Duplicated header
remote controllers
Remote
controller
Remote controller address setting error ---Two remote controllers are set as
header in the double-remote controller control.
*
(* The header indoor unit stops raising alarm and follower indoor units continue
to operate.)
E10
CPU-CPU
communication error
Indoor
Indoor P.C. board --- Communication error between main MCU and motor
microcomputer MCU
Auto-reset
E18
indoor follower unit
regular
Indoor
Indoor P.C. board --- Regular communication is not possible between header
and follower indoor units or between twin header (main) and follower (sub)
units.
Auto-reset
E31
Outdoor Communication error between IPDU and CDB Entire stop
F01
exchanger sensor
Indoor
Heat exchanger sensor (TCJ) , indoor P.C. board --- Open-circuit or short-
circuit of the heat exchanger sensor (TCJ) was detected.
Auto-reset
F02
exchanger sensor
Indoor
Heat exchanger sensor (TC), indoor P.C. board --- Open-circuit or short-circuit
of the heat exchanger sensor (TC) was detected.
Auto-reset
F04
discharge temp.
Outdoor
Outdoor temp. sensor (TD), outdoor P.C. board --- Open-circuit or short-circuit
of the discharge temp. sensor was detected.
Entire stop
F06
Outdoor unit temp.
sensor (TE/TS) error
Outdoor
Outdoor temp. sensors (TE/TS), outdoor P.C. board --- Open-circuit or short-
circuit of the heat exchanger temp. sensor was detected.
Entire stop
TL sensor may be displaced, disconnected or short-circuited.
F08
air temp. sensor
Outdoor
Outdoor temp. sensor (TO), outdoor P.C. board --- Open-circuit or short-circuit
of the outdoor air temp. sensor was detected.
Operation
continued
F10
temp. sensor (TA)
Indoor
Room temp. sensor (TA), indoor P.C. board --- Open-circuit or short-circuit of
the room temp. sensor (TA) was detected.
Auto-reset
TS (1) sensor may be displaced, disconnected or short-circuited.
F13
Outdoor
Abnormal temperature was detected by the temp. sensor of the IGBT heat sink.
Entire stop
F15
Temp. sensor
connection error
Outdoor Temp. sensor (TE/TS) may be connected incorrectly. Entire stop
F29
Indoor unit, other
P.C. board error
Indoor Indoor P.C. board --- EEPROM error Auto-reset
F31
Outdoor Outdoor P.C. board ---- In the case of EEPROM error. Entire stop
H01
compressor
Outdoor
Current detect circuit, power voltage --- Minimum frequency was reached in the
current releasing control or short-circuit current (Idc) after direct excitation was
Entire stop
H02
Outdoor unit
compressor lock
Outdoor Compressor circuit --- Compressor lock was detected. Entire stop
H03
Outdoor unit current
detect circuit error
Outdoor
Current detect circuit, outdoor unit P.C. board --- Abnormal current was
detected in AC-CT or a phase loss was detected.
Entire stop
H04
Case thermostat
operation (1)
Outdoor Malfunction of the case thermostat Entire stop