5
4 INSTALLATION OF PMV KIT
 WARNING
Install the unit securely in the place to sufficiently withstand the weight of the unit.
If the foundation is not sturdy enough, the unit may fall and cause personal injury.
Perform a specified installation work to guard against earthquake.
Improper installation may cause the unit to fall.
REQUIREMENT
To prevent damage on the PMV Kit or personal injury, follow the instructions below.
• Do not step, or put any heavy object on the packed PMV Kit.
• When carrying the PMV Kit, hold the two hanging brackets and be careful not to apply excessive force to
the refrigerant pipes.
External view
EN-7 EN-8
36
76
30
76
Refrigerant pipe connecting port 
(Liquid pipe)
Connection cable 
(accessory)
Refrigerant pipe connecting port 
(Liquid pipe)
226
161
5558 55 30
26
5 REFRIGERANT PIPING
 WARNING
If refrigerant gas has leaked during the installation work, ventilate the room immediately.
If the leaked refrigerant gas comes in contact with fire, noxious gas may be generated.
After the installation work, confirm that refrigerant gas does not leak.
If refrigerant gas leaks into the room and flows near a fire source, such as a fan heater, cooking stove or
heating unit, noxious gas may be generated.
Allowable length of refrigerant piping
PMV Kit
Indoor unit
PMV Kit Indoor unitRefrigerant pipe
2 m to 10 m
Indoor unit
PMV Kit
NO GOOD OK
Label
Attached joint Attached joint
Model name
RBM-PMV0363E
RBM-PMV0903E
Indoor unit capacity type
005, 007, 009, 012 type
015, 018 type
024, 027 type
Diameter of refrigerant pipe
Ø6.4
Ø6.4
Ø9.5
Notes
PMV Kit Attached joint
Seal 
i
eAttached 
oint
Liquid pipe
• Connecting direction of refrigerant pipe
When connecting pipes, be careful of
direction of the main unit.
Be sure to install the main unit so that
[   ] mark in the label directs upward.
For connection of the refrigerant pipes, follow
the arrow mark in the label and connect pipes
after confirming directions of indoor unit and
outdoor unit.
Note)
Do not connect two or more indoor units to one PMV Kit.
Arrange one indoor unit and one PMV Kit set to 1 by 1.
Piping material and dimensions
 CAUTION
When connecting Ø9.5 refrigerant pipes, be sure to insert a seal pipe between PMV main unit and the joint.
If the seal pipe is not inserted, refrigerant leakage is caused.