12
SW2
1
ON
OFF
2 3 4
SW2
5 6 7 8
Weekly timer input switches
Central controller operation can be set when weekly timer
activates (ON/OFF).
123
Timer OFF
ON Timer ON
OFF
All ON All OFF OFF OFF OFF
No change All OFF ON OFF OFF
Individual control
of all indoor units
to be permitted
All indoor units to
be 1*
1
OFF ON OFF
Ditto
All OFF and all
indoor units to be
1*
1
ON ON OFF
Ditto
All indoor units to
be 2*
2
OFF OFF ON
Ditto
All OFF and all
indoor units to be
2*
2
ON OFF ON
Switch No.
Central
controller operation
1
2
3
4
5
6
*All switches are OFF position at shipment.
In case of Remote control mode, use or .
In case of ZONE 1, 2, 3, 4 mode, ALL, all indoor units means
one of ZONE 1, 2, 3, 4.
*
1
: 1 (Central control 1) means ON/OFF operation
cannot execute by remote controller.
*
2
: 2 (Central control 2) means ON/OFF, MODE change.
Temp. setting cannot be executed by remote controller.
1 2
Auxiliary switch
Must be set to OFF position.
Beep tone switch
OFF: Beep tone when each button is pushed.
ON: No tone when each button is pushed.
Indication switch
Normally set to OFF position.
When set to ON position, indication is not displayed on
LCD of central controller.
Fig. 11
OI-607-12EG
01_TCB-SC642TLE_EG_II.fm Page 12 Wednesday, June 30, 2004 4:58 PM

Other manuals for Toshiba TCB-SC642TLE

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TCB-SC642TLE and is the answer not in the manual?

Toshiba TCB-SC642TLE Specifications

General IconGeneral
BrandToshiba
ModelTCB-SC642TLE
CategoryRemote Control
LanguageEnglish

Related product manuals