12
E6582188
Step.8
In advance, tighten 8pcs M8 bolts (not included with this kit) as temporary on panel, and set Inverter with this kit onto
panel.
Temporary tightened bolts pass through larger holes of flanges to hang Inverter with the kit on panel.
For lifting the unit, hang the unit
with wire ropes via hanging holes
provided at both sides of Part (A)
and Part(B).

Other manuals for Toshiba TOSVERT VF-AS3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS3 and is the answer not in the manual?

Toshiba TOSVERT VF-AS3 Specifications

General IconGeneral
ModelTOSVERT VF-AS3
CategoryInverter
Overload Capacity150% for 60 seconds
Cooling MethodForced Air Cooling
Control MethodV/f control, Sensorless vector control
Braking UnitBuilt-in
Communication ProtocolsModbus RTU, DeviceNet, Profibus DP
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat, Ground Fault
EnclosureIP20
Operating Temperature-10°C to +50°C
Humidity5-95% (non-condensing)
AltitudeUp to 1000m