Do you have a question about the Trane 4TTM3060 and is the answer not in the manual?
Warning about live electrical components and potential for serious injury or death.
Warning about live components and ensuring power supply matches equipment nameplate.
Introduction to the subcooling-based charging method to prevent overcharging.
Steps for measuring outdoor ambient, suction line, and liquid line pressures and temperatures.
Using charging tables to find the target liquid temperature based on measured conditions.
Procedure for determining and making adjustments to the refrigerant charge.
Detailed steps for adding or removing refrigerant using the manual charge assist port.
A table correlating system faults with primary and secondary causes.
Steps to measure outdoor ambient, suction line pressure, and liquid line pressure.
Steps to find target liquid temperature, calculate actual and target subcooling.
Calculating the subcooling difference and determining if it's within tolerance.
This document outlines the installation, operation, and maintenance procedures for Trane/American Standard Condensing Units, specifically models 4TTM3018 through 4TTM3060. It serves as an essential guide for individuals with adequate electrical and mechanical experience, emphasizing compliance with national, state, and local codes throughout all installation phases. The manual is intended to remain with the unit as customer property and should be returned to the service information pack upon completion of work.
These condensing units are designed to be a core component of a central air conditioning system, working in conjunction with an indoor unit (air handler or gas furnace) to provide cooling. The system operates by circulating R-410A refrigerant, which absorbs heat from the indoor environment and releases it outdoors. The units are designed for optimal performance and efficiency when installed as part of an approved matched indoor and outdoor system, particularly with TXV (Thermostatic Expansion Valve) indoor systems, which are AHRI rated.
The installation process is broken down into several sections to ensure a systematic and safe setup.
The manual includes sections dedicated to system charge adjustment, checkout procedures, and troubleshooting, which are crucial for maintaining optimal performance.
| Model | 4TTM3060 |
|---|---|
| Refrigerant | R-410A |
| Compressor Type | Scroll |
| Voltage | 208/230V |
| Phase | 1 |
| Cooling Capacity | 60, 000 BTU/hr (5 tons) |
| HSPF Rating | Not Applicable |