48
4TWL9048A-SF-1C-EN
Technician Configuration Menu
SSyysstteemmppaarraammeetteerrssaannddooppttiioonnssaarreerreeppoorrtteeddaanndd
sseettffrroommtthhee CCoonnffiigg MMeennuu..
EXT SWITCH
INACTIVE* ACTIVE
EXT SWITCH
ACTIVE* INACTIVE
MIN AIRFLOW MIN AIRFLOW MIN AIRFLOW
30% FAC TORY 40 % FACTORY 50% FA CTO RY
CLG BLW OFF
NONE DELAY
HTG BLW ON
NONE DELAY
HTG BLW OFF
NONE DELAY
ID AIR CLG
EFF CMFRT
ID AIR HTG
EFF CMFRT
EMI
OFF AUTO
ARE YOUR SURE?
PRESS ENTER <ENTER>
CONFIG MENU
MIN AIRFLOW
FACTORY* FAC TORY
CLG BLW OFF
DELAY* DELAY
HTG BLW ON
DELAY* DELAY
HTG BLW OFF
DELAY* DELAY
ID AIR CLG
CMFRT* CMFRT
ID AIR HTG
CMFRT* CMFRT
EMI
AUTO* AUTO
RESTORE DFLT?
PRESS ENTER <ENTER>
HTG MAX RPM
MED* HIGH
HTG MAX RPM
HIGH* HIGH
HTG MAX RPM
LOW* HIGH
DEFROST TERM
MED FAC TRY*
DEFROST TERM
FACTRY* FAC TRY*
DEFROST TERM
HIGH FAC TRY*
PFC
ON AUTO
PFC
AUTO* AUTO
ALERT
MENU
CONTROL
MENU
Blower Delays Notes
These Blower Delay values are programmed into
the Personaliy Module
Cooling o: 90 Seconds
Heating o: 60 Seconds
Heating on: 30 Seconds
EMI Notes
Introduced with AOC Software Version 2, Fall of 2014.
The drive uses multiple gates (micro relays) to run the
compressor. These gates open and close very quickly. This
high frequency switching generates low levels of electromag-
netic interference that can interact with other devices in the
home; such as televisions, baby monitors, HAM radios, etc.
Changing the EMI setting from AUTO to OFF will alter the
switching frequency during higher speed compressor
operation which will alter the EMI signal.
Contact your local FSR if EMI is still impacting devices after
switching EMI to OFF.
HTG MAX RPM
Introduced with AOC Software
Version 2, Fall of 2014.
Maximum allowed compressor speed percentage over cooling speed.
LOW - Max Htg Speed equals cooling speed (unit has same max compressor speed as a non-variable speed heat pump)
HIGH - allows compressor to run at the max allowed speed based on ambient conditions (full turbo mode)
MED - caps the max compressor speed half way between the low and high speed options
VSPD Side Discharge will be
announced as LOAD SHED
See “13.8 External Shutdown
for more information