EasyManuals Logo

Trane 4TWZ0 series User Manual

Trane 4TWZ0 series
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #9 background imageLoading...
Page #9 background image
18-BC53D2-6 9
STEP 2 - Remove the pressure tap cap and
valve cores from both service valves.
STEP 3 - Purge the refrigerant lines and indoor
coil with dry nitrogen.
STEP 4 - Wrap a wet rag around the valve
body to avoid heat damage and continue the
dry nitrogen purge.
Braze the refrigerant lines to the service
valves.
Continue the dry nitrogen purge. Do not re-
move the wet rag until all brazing is completed.
Important: Remove the wet rag before stopping
the dry nitrogen purge.
NOTE: Precautions should be taken to avoid
heat damage to basepan during brazing. It is
recommended to keep the flame directly off of
the basepan.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane 4TWZ0 series and is the answer not in the manual?

Trane 4TWZ0 series Specifications

General IconGeneral
BrandTrane
Model4TWZ0 series
CategoryAir Conditioner
LanguageEnglish

Related product manuals