EasyManuals Logo

Trane 4TXK6-A User Manual

Trane 4TXK6-A
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #3 background imageLoading...
Page #3 background image
Preface
3
WARNING
R410A Refrigerant under Higher Pressure than R22!
The units described in this manual use R410A refrigerant which operates at 50 to 70%
higher pressures than R-22. Use only R-410A approved service equipment. Refrigerant
cylinders are painted with "pink" color to indicate the type of refrigerant and may
contain a "dip" tube to allow for charging of liquid refrigerant into the system. For
specific handling concerns with R-410A, please contact your
Failure to use R-410A approved service equipment could result in standard equipment
exploding under R-410A higher pressure which could result in death or serious injury.
NOTICE
Use PVE Oil with R-410A Mini-Split Units!
All R-410A mini-splits use a PVE oil (Polyvinyl Ether Oil) that readily absorbs moisture
from the atmosphere. To limit this “hygroscopic” action, the system should remain
sealed whenever possible. If a system has been open to the atmosphere for more than
4 hours, the compressor oil must be replaced. Never break a vacuum with air and
always change the driers when opening the system for component replacement. For
specific handling concerns with PVE oil, contact yo
USE ONLY THE FACTORY RECOMMENDED - DAFNE HERMETIC OIL FV50S - for
servicing these units.
Important!
Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earths naturally
occurring stratospheric ozone layer when released to the atmosphere. In particular, several of
the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine,
Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon
(HCFCs). Not all refrigerants containing these compounds have the same potential impact to the
Responsible Refrigerant Practices
MS-SVN22A-EN
local sales office.
ur
local sales office.
environment. The Compay advocates the responsible handling of all refrigerants, including
industry replacements for CFCs such as HCFCs and HFCs.
The manufacturer believes that responsible refrigerant practices are important to the environment,
our customers, and the air conditioning industry. All technicians who handle refrigerants
must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for
handling, reclaiming, recovering and recycling of certain refrigerants and the equipment
that is used in these service procedures. In addition, some states or municipalities may
have additional requirements that must also be adhered to for responsible management
of refrigerants. Know the applicable laws and follow them.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane 4TXK6-A and is the answer not in the manual?

Trane 4TXK6-A Specifications

General IconGeneral
BrandTrane
Model4TXK6-A
CategoryAir Conditioner
LanguageEnglish

Related product manuals