Precautions for drain lift pipe
The drain lift pipe shall be installed as low as possible .
Tape (White) Drain hos
The drain lift pipe shall be perpendicular to the unit and not more than 300mm away from the unit.
Note:
The slope of accessory drain pipe shall be within 75mm so that the drainage outlet does not necessarily bear
Clamp
excessive external force .
If multiple drain pipes join together, install them as follows .
The size of confluent drain pipe selected shall be suitable for operating capacity of the ur
(2) Check drainage is smooth after installation .
Check drainage by filling in 1200cc water slowly from air outlet or inspection hole .
Installation Instruction for Embedded Air-Conditioning Panel
1 . Before instalation
Warning
The trim panel shall be put on buffer materials when unpacked to prevent being scratched by hard objects.
Please confirm the following accessories delivered with the product:
Bolt (M5*25) Qty: 4
Bolt (M5 25 asket Qty:
Gasket Qty: 4
6 6
T-joint confluent
drain pipe