EasyManua.ls Logo

Trane 4TXK6512G1000AA - 7.4 ODU-EN: Outdoor Unit Installation Site Selection

Trane 4TXK6512G1000AA
187 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
( ) y y
Connect and fix the power supply cable, indoor-outdoor connection cable as following:
For single phase power supply models:
4MXC6518G1000AA,4MXC6524G1000AA,
4MXC6536G1000AA, 4MXC6548G1000AA,
4MXC6560G1000AA
Power supply cable: H05RN-F 3G 4 .0mm
2
Indoor and outdoor connection cable: H05RN-F 4G
2.5mm
2
Wired controller wiring instruction
Alert! Ensure do any of the operating during power off .
A . One Wired controller controls one indoor unit B . Double wired controllers control one indoor unit
Wired
controller
Wired
controller
Wired
controller
C . Connection method for ONE wired controller with MULTIPLE indoor units
For wired controller connect with cassette
Step1:The wiring connection between 1 .wired controller-the master unit(directly connected to the wired controller),
2 .master unit-slave unit, 3 .slave unit-slave unit should be one to one match of all three lines .
The connection wiring is as following, and max . Quantity of the connected indoor units is16 .
6 7
Power supply:
1PH, 220-240V
~, 50/60Hz
L N
Outdoor unit
terminal blocks
Indoor unit
terminal blocks
Cassette
CN1
Cassette
CN1
Cassette 2
Cassette 1 Cassette N Cassette 15 Cassette 16
CN11 CN11-1 CN11 CN11-1 CN11 CN11-1
CN11 CN11-1
CN11 CN11-1
Wired
controller