COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F.
TO CHECK COOLING PERFORMANCE, SELECT THE PROPER INDOOR CFM, ALLOW PRESSURES TO STABILIZE. MEASURE INDOOR WET BULB
TEMPERATURE, OUTDOOR TEMPERATURE, DISCHARGE AND SUCTION PRESSURES. ON THE PLOTS LOCATE OUTDOOR TEMPERATURE (1);
LOCATE INDOOR WET BULB (2); FIND INTERSECTION OF OD TEMP. & ID W.B. (3); READ DISCHARGE OR SUCTION PRESSURE IN LEFT
COLUMN (4).
EXAMPLE: (1) OUTDOOR TEMP. 82 F.
(2) IND
TUAL:
(4) DISCHARGE PRESSURE @ 1200 CFM IS 294 PSIG. DISCHARGE PRESSURE SHOULD BE +/- 10 PSI OF CHART
(5) SUCTION PRESSURE @ 1550 CFM IS 147 PSIG. SUCTION PRESSURE SHOULD BE +/- 3 PSIG OF CHART
DWG.NO. 4WCZ6048B
200
250
300
350
400
450
500
550
40 60 80 100 120
115
125
135
145
155
165
175
185
40 60 80 100 120
115
125
135
145
155
165
175
185
40 60 80 100 120
40
50
60
70
80
90
100
110
120
130
140
150
160
-5 5 15 25 35 45 55 65
200
250
300
350
400
450
500
-5 5 15 25 35 45 55 65
40
50
60
70
80
90
100
110
120
130
140
150
160
-5 5 15 25 35 45 55 65
200
250
300
350
400
450
500
-5 5 15 25 35 45 55 65
Heating with Thermal Expansion Valve
INDOOR ENTERING DRY BULB CURVES TOP TO BOTTOM
80, 70, AND 60 DEG F.
200
250
300
350
400
450
500
550
40 60 80 100 120
Cooling with Thermal Expansion Valve
INDOOR ENTERING WET BULB CURVES TOP TO BOTTOM
71, 67, 63 AND 59 DEG F.
INDOOR ENTERING WET BULB CURVES TOP TO BOTTOM
71, 67, 63 AND 59 DEG F.
INDOOR ENTERING DRY BULB CURVES TOP TO BOTTOM
80, 70, AND 60 DEG F.
OUTDOOR TEMPERATURE (Degree F)
DISCHARGE PRESSURE (PSIG)
SUCTION PRESSURE (PSIG)
OUTDOOR TEMPERATURE (Degree F)
2ND STAGE
2ND STAGE
1ST STAGE
1ST STAGE
2ND STAGE
2ND STAGE
1ST STAGE
1ST STAGE
(1)
(1)
(3)
(3)
(5)
(4)
(2)
(2)
Cooling
Heating