Integrated Furnace Control Menu
IdL
STATUS MENU
Err
ACTIVE ERRORS
Ht tp5
Example
Gas Heat
Example
Tap 5
E3.1
Example
Pressure Switch Error
L6F
LAST 6 FAULTS
E3.1 E04
Example
Pressure Switch Error
Example
Open Limit Switch Error
CR1
Control Release #
CR
Example
Software Version #
COd
Cooing Off Delay
000
090 180
Example
seconds
ODU
Outdoor Stages
1-1
HOD
Heat Off Delay
100 060
Example
seconds
COF
Continuous Fan Tap
CF.1
Example
Tap #
COP
Compressor Operation
Speed Tap
Example
Tap #
Example
Tap #
A801X
Control System Menu Single Stage OD
140
CLEARING THE LAST6 FAULTS:
To clear the stored faults, scroll to the last 6 faults menu,
enter the menu by scrolling to the right and hold the
“Option” key for at least 5 seconds. Release and a set of 3
dashes will be seen 3 times. This confirms the faults have
been cleared.
SETTING UP YOUR SYSTEM:
To change any factory default value, first remove any “call”
from the furnace and allow all fan off delays to finish. ( IDL
should be seen on the display)
Scroll to the selected Menu item by momentarily
depressing the “MENU” key and then depress the
“OPTION” key to the desired setting. Then momentarily
depress the “MENU” key again to save the change.
180
C1.7 C1.1 C1.2 C1.3 C1.4
HtP
Heating Speed Tap
H1.5 H1.1
01
H1.2 H1.6H1.3
Example
Single Stage
SELECTING GAS HEAT FAN SPEEDS:
Airflow can be adjusted while the unit is running.
Scroll to the HTP menu and momentarily push the OPTION key. Tap #5 is the
default setting for all models. When selection is made, momentarily push the
MENU key to save.
If the temperature rise is too high, increase airflow. If the temperature rise too
low, decrease airflow.
NOTE: Tap 9 is not available for gas heating.
run
Run Test Mode
C1.5 C1.6 C1.8 C1.9
H1_7 H1.8H1.4
ORN
LED Orientation
UP
dn
Default Airflow Taps
Gas Heat = Tap 5
ODU Menu 1-1
Cooling / HP = Tap 7
SELECTING COOLING/HP FAN SPEEDS for 1-1 ODU:
Airflow can be adjusted while the unit is running.
Scroll to the
C
OP
menu and momentarily push the OPTION key. Tap 7 is the
default setting for all models. When selection is made, momentarily push the
MENU key to save.
Continuous Fan
Do Not Adjust Above Tap 1
Designated Gas Heang Airflow Taps
A801X026AM2SAC (1-7)
A801X040AM3SAC (1-6)
A801X040BM2SAC (1-8)
A801X060BM3SAC (1-7)
A801X060BM4SAC (1-5)
A801X080BM4SAC (1-6)
A801X080CM5SAC (1-6)
A801X100CM5SAC (1-7)
A801X120DM5SAC (1-7)