20
WSHP-SVX014F-EN
Table 11. Dimensional data right return/top supply (EXVG/DXVG)
Cabinet
Duct
Collar
Duct Collar Location
Blower
Opening
Hi Volt
Nominal
Filter Size
W.I.
NPTI
W.O.
NPTI
Drain
NPTI
Width
Depth Height
Unit A B C D E F G H J K
EXVG009-012 21.50 21.50 34.00 13.25 4.00 1.00 3.50 10.50 9.60 14.25 16 x 19
1/2 1/2 3/4
EXVG015 21.50 23.00 36.00 13.25 4.75 0.63 3.50 10.50 11.30 15.25 17 x 20
3/4 3/4 3/4
EXVG018,
EXVG/
DXVG024
21.50 26.00 38.00 13.25 6.25 0.63 3.50 11.80 11.30 16.25 18 x 23
3/4 3/4 3/4
EXVG030,
EXVG/
DXVG036
24.00 32.50 42.00 17.75 7.25 0.75 3.50 13.70 13.50 18.25 20 x 30 1 1
3/4
EXVG042,
EXVG/
DXVG048
25.40 32.50 49.00 17.75 7.25 0.75 3.50 13.70 13.50 18.25 27 x 30 1 1
3/4
EXVG/
DXVG060-
070
25.40 32.50 55.00 17.75 7.25 0.75 3.50 13.70 13.50 18.25 30 x 33 1 1
3/4
Note: Units in a free return application will require more than a 1 in. clearance to provide proper air flow to the unit’s air-to-refrigerant coil.
Figure 11. Waterside economizer
1
(EXHF/DXHF)
H
M
5"
J
20"
N
G
1 1/2"
L
K
C
D
F
2 1/2"
E
TOP VIEW
FRONT VIEW
A = TO FIELD
SUPPLY PIPING
B = TO FIELD
RETURN PIPING
5/8” 5/8"
UUnniitt DDiimmeennssiioonnss
1.
Waterside economizer installation requires field piping.