EasyManua.ls Logo

Trane Axiom EXHF006 - Page 52

Trane Axiom EXHF006
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
52
WSHP-SVX014F-EN
Table 34. Electrical data - 2 to 6 tons, DX*024-070 (continued)
Model
No.
Unit
Volts
Total
Unit FLA
Comp
RLA
Comp
LRA
Blower
Motor FLA
Blower
Motor
HP
Minimum
Circuit
Ampacity
Maximum
Overcurrent
Protective
Device
Electric
Heat kW
Electric
Heat
Amps
DXVG060
208-230/
60/1
25.0 21.2 104.0 3.8 1
31/31 50/50
0.0 0.0
DXVG060
208-230/
60/3
17.8 14.0 83.1 3.8 1
22/22 35/35
0.0 0.0
DXVG060
460/60/3
8.3 6.4 41.0 1.9 1 10 15 0.0 0.0
DXVG070
208-230/
60/1
31.9 26.9 139.9 5.0 1
39/39 60/60
0.0 0.0
DXVG070
208-230/
60/3
21.5 16.5 110.0 5.0 1
26/26 40/40
0.0 0.0
DXVG070
460/60/3
9.7 7.2 52.0 2.5 1 12 15 0.0 0.0
Table 35. Electrical data - minimum and maximum
Digit 8 Rated Voltage
Hz Ph
Minimum Utilization
Voltage
Maximum Utilization
Voltage
1 208 60 1 197 229
2 230 60 1 207 253
3 208 60 3 187 229
4 460 60 3 414 506
7 265 60 1 239 292
8 230 60 3 207 253
A 208-230 60 1 197 253
B 208-230 60 3 187 253
EElleeccttrriiccaall DDaattaa

Table of Contents

Related product manuals