EasyManua.ls Logo

Trane Axiom EXHF006 - Page 58

Trane Axiom EXHF006
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
58
WSHP-SVX014F-EN
Table 37. Operating pressures in cooling/heating for DX* units (continued)
Operating Data
Model
Entering
Water
Temp
Entering
Water
Temp (°F)
Water
Flow
(GPM)
Cooling Heating
Suction
Pressure
(psig)
Discharge
Pressure
(pgig)
Water
Temp Rise
(°F)
Air Temp
Drop (°F
DB)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp
Drop (°F)
Air Temp
Rise (°F
DB)
DXVG060 45 12.00 136-156 180-230 10-12 22-28 106-122 299-381 6-7 19-28
DXVG060 45 15.00 136-157 174-222 8-10 22-28 108-124 302-384 5-6 20-29
DXVG060 55 12.00 138-159 210-267 10-12 22-27 121-139 313-398 7-9 22-32
DXVG060 55 15.00 138-159 203-259 8-10 22-27 124-142 315-401 6-7 23-33
DXVG060 68 12.00 141-162 251-320 9-12 21-27 143-165 333-424 8-10 27-37
DXVG060 68 15.00 141-162 245-312 8-10 21-27 147-170 335-427 7-8 28-38
DXVG060 75 12.00 143-164 275-350 9-12 21-27 158-181 343-436 9-11 29-40
DXVG060 75 15.00 143-164 269-342 7-10 21-27 162-187 345-439 7-9 30-40
DXVG060 86 12.00 146-167 316-402 9-12 20-26 184-211 361-460 10-13 33-44
DXVG060 86 15.00 145-167 310-394 7-9 20-26 189-218 364-463 8-10 34-45
DXVG060 95 12.00 148-170 353-450 9-12 20-26
DXVG060 95 15.00 148-170 347-442 7-9 20-26
DXVG070 32 14.00 89-102 277-353 4-6 16-25
DXVG070 32 17.50 91-104 278-354 4-5 17-25
DXVG070 45 14.00 130-150 171-218 11-14 23-28 107-123 296-376 6-7 20-30
DXVG070 45 17.50 130-150 167-213 8-11 23-28 110-126 298-379 5-6 21-30
DXVG070 55 14.00 132-151 199-254 10-13 22-28 122-140 312-397 6-8 23-33
DXVG070 55 17.50 131-151 194-247 8-11 22-28 125-144 314-400 5-7 24-34
DXVG070 68 14.00 136-156 237-302 10-13 22-28 144-165 333-424 8-10 28-38
DXVG070 68 17.50 136-156 232-295 8-11 22-28 148-170 336-428 6-8 28-39
DXVG070 75 14.00 139-160 260-331 10-13 22-27 157-181 345-439 8-11 30-40
DXVG070 75 17.50 139-159 254-324 8-11 22-27 162-187 348-443 7-9 31-41
DXVG070 86 14.00 143-164 300-382 10-13 21-27 183-211 363-462 10-12 34-45
DXVG070 86 17.50 142-164 294-374 8-10 21-27 189-218 367-467 8-10 35-45
DXVG070 95 14.00 145-166 336-427 10-13 21-26
DXVG070 95 17.50 144-166 330-420 8-10 21-26
Table 38. Operating pressures in cooling/heating for EX* units
Operating Data
Model
Entering
Water
Temp
Entering
Water
Temp
F)
Water
Flow
(GPM)
Cooling Heating
Suction
Pressure
(psig)
Dis-
charge
Pressure
(pgig)
Water
Temp
Rise (°F)
Air Temp
Drop (°F
DB)
Suction
Pressure
(psig)
Dis-
charge
Pressure
(psig)
Water
Temp
Drop
F)
Air Temp
Rise (°F
DB)
EXHF006 35 1.40 94-108 279-355 6-8 23-29
EXHF006 35 1.70 96-110 281-357 5-6 23-29
EXHF006 45 1.40 143-165 190-243 13-16 24-30 110-127 297-377 7-9 26-34
EXHF006 45 1.70 143-164 184-235 11-13 24-31 113-130 300-382 6-8 27-34
EXHF006 55 1.40 145-167 217-277 13-16 23-30 128-147 317-404 8-10 30-39
SSttaarrtt UUpp