44
RLC-SVX023B-GB
Maintenance Procedures
Figure 10 –
Oil Filter Replacement Chart
Unit shut down
Minimum system pressure differential
= 25 psid
Clean Filter below this line
Recommend replacing filter
Start protection line for 1st
2.5 minutes of operation
Run protection line after 2.5
minutes of operation
GP2 / RTWD Clean Filter Versus Recommended Filter Replacement
Line
CH530 RTWD Oil Pressure Protection Scheme
Recommended replacing lter
Clean Filter below this line
Run protection line after 2.5
minutes of operation
Start protection line for 1st
2.5 minutes of operation
GP2 Clean Filter Versus Recommended Filter Replacement
Line UC800 RTSF Pressure Protection Scheme
Unit shut down
Minimum system pressure differential
= 25 psid