40 OAU-SVX006E-EN
System Configuration and Pre-Start
The following procedure must be completed prior to
performing the startup procedure in “Startup,” p. 52. This
section d
escribes procedures to navigate the various
displays on the Unit Display and configure the Outdoor Air
Unit Main Unit Display system setpoints and operating
parameters.
Important: T
h
is section is intended to provide
guidelines for navigation through the
remote operator display screens. For
additional control system information, refer
to Integration Guide: Tracer™ UC600
Programmable Controller for Packaged
Outdoor Air Unit (BAS-SVP18*-EN). The
unit is configured at the factory with the
default settings as described in sequence of
operation and the details concerning setup
and operating setpoints.
Table 8. Chart of analog and binary input/output
# BACnet Point Name Write Default Range Units Description
AI-01
Space Temperature
Local
40–95 °F
Hardwired input from field installed space
tempe
rature sensor, wired to OAUTS-1 & -2
(SPTC).
AI-02 Space Humidity Local 0–100 %
Hardwired input from field installed space humidity
s
e
nsor,
wired to OAUTS-5 & -6 (SPHC).
AI-03
Supply Fan Piezo
Pr
essure Local
0–25 in.H
2
O
Hardwired input from factory installed piezo
differen
tial
pressure sensor (SPZ).
AI-04
Outdoor Coil Leaving
Tem
perature
Circuit 1 Local
-50–270 °F
Hardwired input from factory installed temperature
sensor
located on the outdoor coil (CCTC1).
AI-05
Outdoor Coil Leaving
Tem
perature
Circuit 2 Local
-50–270 °F
Hardwired input from factory installed temperature
sensor
located on the outdoor coil (CCTC2).
AI-06
Return Air Temperature
Local
-40–135 °F
Hardwired input from factory installed temperature
se
nsor
located in the return air path (RTC).
AI-07
Outdoor Air Damper
Pos
ition Status
Local
0-100 %
Hardwired input that provides feedback status
from the
actuator located on the outdoor air damper (OAD).
AI-08
Space CO
2
Concentration Local
- ppm Hardwired input from field provided CO2.