System Configuration and Pre-Start
42 OAU-SVX006E-EN
AO-01
Hot Gas Reheat Valve
Co
mmand
0–100 % Analog hot gas reheat output.
AO-02
Supply Fan Speed
Co
mmand
0–100 % Supply fan speed output.
AO-03
Compressor Speed
Co
mmand Circuit 1
0–100 %
Speed control for circuit 1 digital scroll or variable
sp
eed
compressor.
AO-04
Exhaust Fan Speed
O
utput Command
0–100 % Exhaust fan speed output
AO-05
Outdoor Air Damper
P
osition Command
0–100 %
Position command for outdoor air damper. Return
ai
r
damper position is inverse to this output.
AO-06
Energy Recovery
Outd
oor Air Bypass
Position Command
0–100 %
Analog output for modulating ERV outdoor air
by
pass.
AO-07
Condenser Fan Speed
Co
mmand
0–100 % Analog condenser fan speed command.
AO-08
Compressor Speed
Co
mmand Circuit 2
0–100 %
Speed control for circuit 1 digital scroll or variable
sp
eed
compressor.
AO-09
Chilled Water Valve
Co
mmand
0–100 %
Analog chilled water actuator valve output
command.
AO-10
Energy Recovery Wheel
Spe
ed
Command
0–100 % Analog ERV VFD command.
AO-11
Heating Output
Co
mmand
0–100 %
Analog heating output command. Modulating
bu
rner only
for gas heat.
AO-12
Second Stage
Co
ndenser Fan Speed
Command
0–100 %
Analog condenser fan speed command for the
second
stage.
AO-13
Energy Recovery
Exhaus
t Air Bypass
Position Command
0–100 %
Analog output for modulating ERV exhaust air
by
pass.
AV-01
Occupied Cooling
Set
point
72°F 55–85 °F Space cooling setpoint used in occupied mode.
AV-02
Occupied Heating
Set
point
70°F 55–85 °F Space heating setpoint used in occupied mode.
AV-04
Heat Pump Disable
Te
mperature
25°F 0–60 °F
Heat pump operation is disabled when the outdoor
ai
r
temperature falls below this setpoint.
AV-05
Dehumidification
Te
mperature Active
-58–482 °F
Temperature reading for dehumidificaiton. For OAN
R
ev. 6 cabinets this is discharge air dewpoint, all
other it's indoor
coil leaving temperature.
AV-07 Space Humidity Active 0–100 % Actively used space relative humidity.
AV-08 Space Humidity BAS 0–100 %
Communicated space relative humidity. Takes
pr
iority over
hardwired input when put In Service.
AV-10
Outdoor Air Dewpoint
Enab
le Setpoint
55°F 45–100 °F Setpoint used to put the unit into dehumidification.
AV-11 Outdoor Air Dewpoint -10–150 °F
Dewpoint of the outdoor air. This point is calculated
within
the program.
AV-12
Exhaust Fan Tracking
Offset Setpo
int
0.9 0–150 %
Setpoint used to track with the supply fan speed.
F
actory default is Out of Service. When put In
Service it takes priority over other exhaust fan
control schemes.
Table 8. Chart of analog and binary input/output (continued)
# BACnet Point Name Write Default Range Units Description

Table of Contents