System Configuration and Pre-Start
OAU-SVX006E-EN 49
MV-10 Supply Fan Wheel Size – Factory set supply fan size.
MV-11 Direct Fired Burner Size – Factory set direct fired burner size.
MV-12 Exhaust Fan Wheel Size – Factory set exhaust fan size.
MV-13 Program Control Type ● #N/A
1 = Space Control
2 = Discharge Control 3 = Single Zone VAV 4 =
Mul
ti Zone VAV
5 = Critical Space Control
6 = Critical Discharge Control
MV-16
Dehumidification
Sy
stem Status
1 = Off
2 = On
MV-17
Economizer System
Status
1 = Not Economizing 2 = Economizer Mode
3 = Free Cooling Mode
4 = Ventilation Mode
MV-19
Compressor 1 Status
Acti
ve
1 = Disabled
2 = Enabled, No Running Status 3 = Enabled With
Running Status 4 = Enabled, No VFD Alarm
5 = Not Installed
MV-20
Compressor 2 Status
Acti
ve
1 = Disabled
2 = Enabled, No Running Status 3 = Enabled With
Running Status 4 = Not Installed
5 = Input Status In Fail
MV-21
Compressor 3 Status
Acti
ve
See Compressor 2 Status Active MV-20
MV-23
Compressor 4 Status
Acti
ve
See Compressor 2 Status Active MV-20
MV-24
Compressor 5 Status
Acti
ve
See Compressor 2 Status Active MV-20
MV-25
Compressor 6 Status
Acti
ve
See Compressor 2 Status Active MV-20
Table 8. Chart of analog and binary input/output (continued)
# BACnet Point Name Write Default Range Units Description