Alarms and Troubleshooting
OAU-SVX006E-EN 69
Table 14. Diagnostic values
Name Manual or Auto Reset Possible Causes
BV-01 Diagnostic: Supply Fan Failure
Manual Reset. Occurs when the
sup
ply fan is commanded on but
the proving switch does not close
after two minutes
VFD not operating OA and/or RA dampers not operating
properly
Indoor Fan Motor Failure
Indoor Fan Failure Switch IFFS (pressure) failure
IFFS tubing damaged or not properly connected
BV-02
Diagnostic: Discharge Air
H
umidity Source Failure
Auto Reset. Occurs when the
di
scharge air humidity sensor falls
outside of range
BAS communication down
Failed sensor or improper sensor installation
Humidity Wiring Polarity sensitive
BV-03
Diagnostic: Outdoor Air Damper
End
Switch
Auto Reset. Occurs when there is a
call
for the two-position outdoor air
damper but the end switch has no
made for 180 seconds
No voltage on actuator
Failed OAD power transformer
No continuity thru end switch ( check at UC)
BV-06
Diagnostic: Discharge Air
T
emperature Source Failure
Auto Reset. Occurs when the
di
scharge air temperature sensor
falls outside of range
BAS Communication Down
Failed sensor or improper sensor installation
BV-08 Diagnostic: Fire Shutdown
Auto Reset. Diagnostic from BAS
communi
cation. Unit resets once
this returns to normal
•BAS only
BV-10
Diagnostic: Low Discharge Air
Te
mp Lockout
Manual Reset. Occurs when the
di
scharge air temperature is below
35°F for five minutes, or ten
minutes during heat pump defrost
mode
Heat Overridden OFF
Compressor(s) Overridden ON
Setpoint Failures Incorrect
DAT sensor malfunction
BV-11
Diagnostic: Space Temperature
Sou
rce Failure
Auto Reset. Occurs when the space
temperature active falls outside of
ra
nge
BAS communication down
Failed sensor or improper sensor installation
BV-13
Diagnostic: Outdoor Air
T
emperature Source Failure
Auto Reset. Occurs when the
outd
oor air humidity active falls
outside of range
BAS Communication Down
Failed sensor or improper sensor installation
BV-14
Diagnostic: Outdoor Air Humidity
Sou
rce Failure
Auto Reset. Occurs when the
outd
oor air temperature active falls
outside of range
BAS communication down
Failed sensor or improper sensor installation
Humidity Wiring Polarity sensitive
BV-15
Diagnostic: High Discharge Air
Te
mp Lockout
Manual Reset. Occurs when the
di
scharge air temperature is above
130°F for five minutes
Heat Overridden ON
Low discharge air volume
Dirty Air filters
High gas heater manifold pressure
OA/RA damper position incorrect
High temp limit not properly installed or wired
DAT sensor malfunction