Alarms and Troubleshooting
OAU-SVX006E-EN 71
BV-42 Diagnostic: Heat Failure
Auto Reset (4 hours). Occurs when
there is a
call for heat but the heat
status relay is not energized. The
heat is cycled three times and then
locked out for four hours before
retrying
Trips after heat command ON and no GV status offer 1 minute
No gas, low gas pressure or high gas pressure to unit
Unit Manual shutoffs closed
Heater inducer failure
Heat relay failure
Loose or incorrect wiring
BV-46
Diagnostic: Not Economizing
W
hen It Should Be Economizing
Auto Reset
Occurs when the unit is in economizer mode and the outdoor
ai
r damper feedback status is greater than 20% lower than
the output.
BV-47
Diagnostic: Return Duct/Space
Pr
essure Setpoint Range
Auto Reset
Occurs when the duct static setpoint is above 85% of the
maximum li
mit for the hardwired input, below 5% of the full
scale input, or less than the minimum.
BV-48
Diagnostic: Damper Not
Mo
dulating
Auto Reset
Occurs when the outdoor air damper position feedback is
more more than 20% off than the output.
BV-50
Diagnostic: Space CO2 Source
Fa
ilure
Auto Reset Occurs when the space CO2 read
ing falls outside of range.
BV-52
Diagnostic: Compressor 2 Run
Fa
ilure
Manual or Auto Reset
Occurs when there is a call for a compressor without a run
status for five minutes. Auto resets after three hours.
BV-53
Diagnostic: Compressor 3 Run
Fa
ilure
Manual or Auto Reset
Occurs when there is a call for a compressor without a run
status for five minutes. Auto resets after three hours.
BV-54
Diagnostic: Compressor 4 Run
Fa
ilure
Manual or Auto Reset
Occurs when there is a call for a compressor without a run
status for five minutes. Auto resets after three hours.
BV-55
Diagnostic: Return Duct/Space
Pr
essure Source Failure
Auto Reset
Occurs when the return duct/space pressure transducers falls
outside of range.
BV-56
Diagnostic: Outdoor Air Flow
Se
nsor Source Failure
Auto Reset
Occurs when the outdoor air damper is above 15% and the
outdoor air flow measurement shows less than 50cfm.
BV-58
Diagnostic: Compressor 5 Run
Fa
ilure
Manual or Auto Reset
Occurs when there is a call for a compressor without a run
status for five minutes. Auto resets after three hours.
BV-59
Diagnostic: Compressor 6 Run
Fa
ilure
Manual or Auto Reset
Occurs when there is a call for a compressor without a run
status for five minutes. Auto resets after three hours.
BV-60
Diagnostic: Energy Recovery
W
heel Rotation Failure
Auto Reset
Occurs when there is a call for the ERV but rotation was not
detected for five minutes.
Table 14. Diagnostic values (continued)
Name Manual or Auto Reset Possible Causes