OAU-SVX006E-EN 73
Appendix
OAU Filter Guide
Table 16. OAD units
Evaporator
Thickness, in. (cm) MERV Qty Height, in. (cm) Width, in. (cm)
2 (5.1) 8, 13 6 24 (63.5) 18 (45.7)
4 (10.2) 14 6 24 (63.5)
18 (45.7)
ERV Module
Return Air
Thickness, in. (cm) MERV Qty Height, in. (cm) Width, in. (cm)
2 (5.1) 8 6 20 (50.8) 20 (50.8)
Outside Air
(a)
Thickness, in. (cm) MERV Qty Height, in. (cm) Width, in. (cm)
2 (5.1) 8 6 20 (50.8) 20 (50.8)
Inlet Hood
Thickness, in. (cm) Material Qty Height, in. (cm) Width, in. (cm)
2 (5.1) Aluminum Mesh 6 20 (50.8) 20 (50.8)
(a) No filters will be provided on the outside air path of the ERV section if electric preheat is provided.
Table 17. OAN units
Evaporator (40 to 50 ton - 4 and 6 row coils; 55 to 100 ton - 6 row coils)
Thickness, in. (cm) MERV Qty Height, in. (cm) Width, in. (cm)
2 (5.1) 8, 13 15 20 (50.8) 18 (45.7)
4 (10.2) 14 15 20 (50.8)
18 (45.7)
Evaporator (55 to 100 ton - 4 row coils)
Thickness, in. (cm) MERV Qty Height, in. (cm) Width, in. (cm)
2 (5.1) 8, 13 12 20 (50.8) 25 (63.5)
4 (10.2) 14 12 20 (50.8)
25 (63.5
ERV Module
Return Air
Thickness, in. (cm) MERV Qty Height, in. (cm) Width, in. (cm)
2 (5.1) 8 15 24 (61.0) 18 (45.7)
Outside Air
(a)
Thickness, in. (cm) MERV Qty Height, in. (cm) Width, in. (cm)
2 (5.1) 8 15 24 (61.0) 18 (45.7)
Inlet Hood
Thickness, in. (cm) Material Qty Height, in. (cm) Width, in. (cm)
2 (5.1) Aluminum Mesh 12 24 (61.0) 24 (61.0)