Startup Form
94 OAU-SVX006E-EN
Typical Setpoints
# BACnet Point Name Setting Default Range Units Description
DISCHARGE AIR CONTROL
AV-29
Outdoor Air Cooling
Ena
ble Setpoint
- 45–100 °F
When the Outdoor Air Temperature is above this setpoint, the unit will
be locked into Cooling Mode.
AV-33
Outdoor Air Heating
Ena
ble Setpoint
- 15–75 °F
When the Outdoor Air Temperature is below this setpoint, the unit will
be lock
ed into Heating Mode (takes priority over Dehumidification
Mode).
AV-10
Outdoor Air Dewpoint
Ena
ble Setpoint
- 45–100 °F
When the Outdoor Air Dewpoint is above this setpoint, the unit will be
locked into Dehumidification Mode (takes priority over Cooling Mode).
AV-30
Discharge Air Cooling
Set
point BAS
60 45–90 °F Discharge air setpoint during Cooling and Dehumidification Mode.
AV-32
Discharge Air Heating
Set
point BAS
65 45–100 °F Discharge air setpoint during Heating Mode.
AV-67
Discharge Air
Te
mperature Setpoint
BAS
55 40–125 °F
Discharge air setpoint used during Heating, Cooling, and
Dehumidification Mode. Factory defaulted Out of Service, put In
Service to use.
SPACE CONTROL AND SINGLE ZONE VAV
AV-87
Space Humidity
Set
point
45 0–100 %
Temperature setpoint and this setpoint is used to calculate a Space
Dewpoint Setpoint, which puts the unit into Dehumidification Mode.
AV-01
Occupied Cooling
Set
point
72 55–85 °F Space cooling setpoint used in occupied mode.
AV-02
Occupied Heating
Set
point
70 55–85 °F Space heating setpoint used in occupied mode.
AV-25
Space Temperature
Set
point BAS
72 62–80 °F
Communicated space temperature setpoint (overwrites Occupied
Cooling and Heating Setpoints). Factory defaulted Out of Service, put
In Service to use.
MULTI ZONE VAV
AV-10
Outdoor Air Dewpoint
Ena
ble Setpoint
55 45–100 °F
When the Outdoor Air Dewpoint is above this setpoint, the unit will be
locked into Dehumidification Mode (takes priority over Cooling Mode).
AV-30
Discharge Air Cooling
Set
point BAS
60 45–90 °F Discharge air setpoint during Cooling and Dehumidification Mode.
AV-32
Discharge Air Heating
Set
point BAS
65 45–100 °F Discharge air setpoint during Heating Mode.
AV-67
Discharge Air
T
e
mperature Setpoint
BAS
55 40–125 °F
Discharge air setpoint used during Heating, Cooling, and
Dehumidification Mode. Factory defaulted Out of Service, put In
Service to use.
AIR BALANCE
AV-39
Supply Fan Air Flow
Set
point
Varies 0–25000 cfm
Setpoint used to control the supply fan for constant volume. Only
used on OAB and OAG cabinets (not VAV).
AV-46
Duct Static Pressure
Set
point BAS
1.5 -1–6 in.H2O
Setpoint used to control supply fan to static pressure. Factory default
range is 0-2"WC, but can be re-configured for 0-5"WC.
AV-40
Exhaust Fan Speed
Set
point BAS
80 0–100 %
Setpoint used for constant speed exhaust fan. Used on OAD, OAK, and
OAN
cabinets that have exhaust, but do not have modulating OA/RA
dampers.
AV-57
Exhaust Fan Air Flow
Set
point
Varies 0–25000 cfm
Setpoint used for constant volume exhaust fan control. Used on OAB
and OAG cab
inets that have exhaust, but do not have modulating OA/
RA dampers.
AV-48
Outdoor Air Damper
Minimum Po
sition
Setpoint
Varies 0–100 %
Setpoint used to limit the outdoor air damper position during all
operation. Typically adjusted during air balance. Factory set at an
estimate based on submittal data.