Startup Checklists
Table 58. Critical control parameters
Notes:
1. Using the Human Interface (HI), go to SETUP Menu and input setting for parameters listed below.
2. Use the map shown below to determine region of country based on unit site location.
Suggested
Parameter
Economizer Settings
Region 1 Region 2 Region 3 Region 4 Region 5 Region 6 Region 7
Supply Air Temperature Control Setpoint 8°F
Supply Air Temperature Deadband 55 °F
Supply Air Pressure Setpoint 1.8" w.c.
Supply Air Pressure Deadband 0.1" w.c.
Building Static Pressure Setpoint 0.03" w.c.
Building Static Pressure Deadband 0.04" w.c.
Standby Freeze Avoidance 20%
Exhaust Enable Setpoint 10%
Economizer Minimum Position Setpoint 10%
Fixed Dry Bulb Economizer C/O
Type a (Moist)*
T
OA
> 65°F T
OA
> 65°F T
OA
> 65°F T
OA
> 65°F T
OA
> 70°F T
OA
> 70°F T
OA
> 70°F
Fixed Dry Bulb Economizer C/O
Type b (Dry)*
T
OA
> 75°F
Fixed Dry Bulb Economizer C/O
Type c (Marine)*
T
OA
> 75°F T
OA
> 75°F T
OA
> 75°F
Fixed Reference
Enthalpy Changeover
H
OA
> 28 Btu
Differential Comparative
Enthalpy Changeover
H
OA
> H
RA
Note: See map (Figure 88, p. 173) below for dry bulb changeover.
Examples:
(a) Minneapolis, Minnesota is in “Region 6” and resides in “Moist” subregion, thus designation is 6b. Economizer changeover setting
should be 75°F.
(b) Charleston, South Carolina is in “Region 3” and resides in “Moist” subregion, thus the designation is 3c. Economizer changeover setting
should be 65°F.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane IntelliPak SAHL Series and is the answer not in the manual?

Trane IntelliPak SAHL Series Specifications

General IconGeneral
BrandTrane
ModelIntelliPak SAHL Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals