SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of
heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training.
Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.
When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that
are attached to the equipment.
October 2013
RT-SVX36K-EN
Installation, Operation,
and Maintenance
IntelliPak™
Commercial Rooftop Air Conditioners
with CV, VAV, or SZVAV Controls
A and later Design S equence
SAHL
*20, *25, *30, *40, *50, *55, *60, *70, *75
SEHL, SFHL, SLHL, SSHL, SXHL
*20, *25, *30, *40, *50, *55, *60, *70, *75,
*24, *29, *36, *48, *59, *73, *80, *89
SXHK, SEHK, SFHK, SLHK, SSHK
*90, *11, *12, *13

Table of Contents

Other manuals for Trane IntelliPak

Questions and Answers

  • C
    christopher31Aug 17, 2025
    What does it mean if my Trane IntelliPak shows Low Suction Pressure?
    • R
      rebeccamooreAug 17, 2025
      The suction pressure dropped below a pressure threshold. See the Low Suction Pressure Protection specification for further details.
  • K
    Kim LopezAug 19, 2025
    What does it mean if my Trane Air Conditioner displays VFD Supply Fan Motor Current Overload - 1?
    • C
      Curtis ArmstrongAug 20, 2025
      The inverter peak current of approximately 200% of rated current was exceeded for 1.5 seconds. This will generate Supply Fan 1 Proving Failure Diagnostic and lockout all heating operation. Also, Supply Fan 1 Proving Failure will be generated to shutdown the unit.
  • A
    Ashley GonzalezAug 22, 2025
    What does it mean if my Trane IntelliPak displays VFD Supply Fan Motor Current Overload - 2?
    • E
      emily95Aug 22, 2025
      The inverter peak current of approximately 200% of rated current was exceeded for 1.5 seconds, generating Supply Fan 2 Proving Failure Diagnostic and locking out all heating operation. Additionally, Supply Fan 2 Proving Failure will be generated to shut down the unit.
  • A
    andre82Aug 25, 2025
    What does it mean if my Trane IntelliPak is in Emergency Override Mode Shutdown?
    • A
      Alicia MedinaAug 26, 2025
      The unit is following Emergency Override Shutdown, meaning all burners on the manifold are unavailable.
  • J
    Janet BarrettAug 28, 2025
    What does it mean if my Trane IntelliPak displays VFD Condenser Fan Motor Current Overload – Cktx?
    • N
      Natasha LoganAug 28, 2025
      The inverter peak current of approximately 200% of rated current was exceeded for 1.5 seconds. As a result, condenser fan control will revert to a fixed-speed fan algorithm using the remaining fans.
  • J
    James Grant DDSAug 30, 2025
    What happens when the Discharge Air Iso Damper fails to open on my Trane IntelliPak?
    • N
      Nathan HardyAug 30, 2025
      The Discharge Air Isolation Damper operation was less than 80% open after 5 minutes, meaning all burners on the manifold are unavailable.
  • C
    Christopher BraunSep 2, 2025
    What does it mean if my Trane Air Conditioner displays VFD Relief Fan Power Mod Overheated – x?
    • R
      Ricardo BellSep 2, 2025
      The Rectifier thermocouple has reached a too-high temperature. (Motor Manual Reset) Other fans are available with a warning only.
  • D
    Daniel BriggsSep 4, 2025
    What does it mean if my Trane IntelliPak displays VFD Relief Fan Motor Overheated – x?
    • G
      George StephensSep 5, 2025
      The motor thermocouples have reached a too-high temperature. (Motor Manual Reset) Other fans are available with a warning only.
  • M
    Mitchell MillerSep 8, 2025
    What does Comm Loss: Condenser Fan Relay 1 Cktx mean on my Trane Air Conditioner?
    • J
      Jennifer White MDSep 8, 2025
      There has been a continual loss of communication between the MP and the Functional ID for a 30-second period, which will initiate shutdown actions.
  • T
    Tammy HunterSep 10, 2025
    What does it mean if my Trane Air Conditioner displays VFD Relief Fan Locked Motor - x?
    • T
      troycastroSep 10, 2025
      Something has blocked the rotor from turning. (Motor Auto Reset) Other fans are available with a warning only.

Trane IntelliPak Specifications

General IconGeneral
RefrigerantR-410A
Compressor TypeScroll
Voltage208/230/460V, 3-phase
TypeRooftop Unit
Airflow ConfigurationHorizontal
Sound LevelVaries by model
Control SystemTracer
DimensionsVaries with model
WeightVaries with model
Heating CapacityOptional electric or gas