RT-SVX36G-EN 81
Installation
Emergency Override Definitions (with LCI-I/BCI-I module installed)
When an LCI-I/BCI-I module is installed, the user can initiate one of five (5) Emergency Override
sequences that have the following predefined unit operation:
PRESSURIZE
Supply Fan - On
Inlet Vanes - Open (if equipped)
Exhaust/Return Fan - Off (if equipped)
Exhaust/Return Dampers - Closed (if equipped)
OA Dampers - Open
Heat - All heat stages Off (staged gas and elec.), Hydronic
Heat & Mod Gas Heat output at 0%.
Occupied/Unoccupied output - Energized
VO Relay - Energized (with VOM module installed)
OA Preheater State - Off (with VCM module installed)
DEPRESSURIZE
Supply Fan - Off
Inlet Vanes - Closed (if equipped)
Exhaust/Return Fan - On (if equipped)
Exhaust/Return Dampers -Open (if equipped)
OA Dampers - Closed
Heat - All heat stages Off (staged gas and elec.), Hydronic
heat & Mod Gas Heat output at 0%.
Occupied/Unoccupied output - De-energized
VO Relay - Energized (with VOM module installed)
OA Preheater State - Off (with VCM module installed)
PURGE
Supply Fan - On
Inlet Vanes - Open (if equipped)
Exhaust/Return Fan - On (if equipped)
Exhaust/Return Dampers - Open (if equipped)
OA Dampers - Open
Heat - All heat stages Off (staged gas and elec.), Hydronic
Heat & Mod Gas Heat output at 0%.
Occupied/Unoccupied output - Energized
VO Relay - Energized (with VOM module installed)
OA Preheater State - Off (with VCM module installed)
SHUTDOWN
Supply Fan - Off
Inlet Vanes - Closed (if equipped)
Exhaust/Return Fan - Off (if equipped)