[ VII Microprocessor Control ]
- 16 -
HWE1832A GB
In the air: Detected that the float switch is OFF for 15 seconds.
4. Heat operation
1. Thermo regulating function
(1) Thermo regulating function (Function to prevent restarting for 3 minutes)
Room temperature desired temperature -2°F ···Thermo ON
Room temperature desired temperature ···Thermo OFF
2. Fan
(1) By the remote controller setting (switch of 3 speeds+Auto)
When [Auto] is set, fan speed is changed depending on the value of:
Desired temperature - Room temperature
Give priority to under-mentioned controlled mode
1) Hot adjust mode
2) Preheating exclusion mode
3) Thermo OFF mode (When the compressor off by the thermoregulating)
4) Cool air prevention mode (Defrosting mode)
5) Capacity increasing mode
(2) Hot adjust mode
The fan controller becomes the hot adjuster mode for the following conditions.
1) When starting the Heat operation
2) When the thermoregulating function changes from OFF to ON.
3) When release the Heat defrosting operation
A: Hot adjust mode starts.
B: 5 minutes have passed since the condition A or the indoor liquid pipe temperature turned 95°F or more.
C: 2 minutes have passed since the condition A. (Terminating the hot adjust mode)
*1 "STAND BY" will be displayed during the hot adjust mode.
<How to operate>
1. Press POWER [ON/OFF] button.
2. Press the [F1] button to display Heat.
3. Press the [F2] or [F3] button to set the desired temperature.
The set temperature changes 2°F when the [F2] or [F3] button is
pressed one time. Heating 63 to 83°F.
<Display in Heat operation>
[DEFROST]
The [DEFROST] symbol is only displayed during the defrost op-
eration.
[STANDBY]
The [STANDBY] symbol is only displayed during the hot adjust
mode.
Type Fan speed notch
3 speeds + Auto type [Low], [Med], [High], [Auto]
ON
OFF
15sec. 15sec. 15sec. 1min.30sec. 1min.30sec.
Float SW
In the water In the air In the water Error
postponement
Drain pump
abnormal
CAB
[Extra Low]
[Low]
Set fan speed by the remote controller
Hot adjust mode *1