INSTALLATION INSTRUCTIONS
AIR HANDLERS
WARNING
These instructions are intended as an aid to qualified licensed
service personnel for proper installation, adjustment and
operation of this unit. Read these instructions thoroughly before
attempting installation or operation. Failure to follow these
instruction may result in improper installation, adjustment,
service or maintenance possibly resulting in fire, electrical
shock, property damage, personal injury or death.
RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION
DO NOT DESTROY THIS MANUAL
Please read carefully and keep in a safe place for future reference by a serviceman.
1.5-5Tons J4AH4P SERIES
FEATURING R410A OR R22 REFRIGERANT
HIGH EFFICIENCY
BX-SVN-J4AH4P-1A-EN
Question and Answer IconNeed help?

Do you have a question about the Trane OXBOX J4AH4P30A1B00AA and is the answer not in the manual?

Summary

Safety Information

General Installation Guidelines

Unit Dimensions

Details physical dimensions, weight, and supply duct sizes for various models.

Applications and Configurations

Vertical Upflow Installation

Describes the standard factory configuration for vertical upflow installation and related ductwork.

Vertical Downflow Conversion

Explains conversion to downflow and breaker switch orientation requirements.

Horizontal Installation

Details conversion to horizontal left-hand supply and secondary drain pan recommendations.

Electrical Wiring Procedures

Power Wiring

Covers requirements for supply circuit power wiring, disconnects, and connection points.

Control Wiring

Provides guidance on low voltage control wiring separation, wire gauge, and connections.

Grounding Requirements

Emphasizes permanent grounding necessity and methods for safe electrical installation.

Electrical Data

Presents electrical specifications including voltage, amps, HP, speeds, and circuit protection for models.

Electric Kit MCA;MOP Data

Lists ampacity and circuit breaker/fuse data for various electric heat kits and air handler models.

Airflow Performance

Ductwork Installation

Refrigerant Connections and Condensate Drain

Condensate Drain Tubing

Details proper installation of condensate drain lines, traps, and testing procedures.

Air Filter Requirements

Filter Installation Dimensions

Wiring Diagrams

Overview

This document provides installation, adjustment, and operation instructions for the Oxbox J4AH4P Series High-Efficiency Air Handlers, designed for 1.5-5 ton systems using R410A or R22 refrigerant. It is intended for qualified, licensed service personnel to ensure proper and safe installation and maintenance.

Function Description

The Oxbox J4AH4P Series Air Handlers are designed to provide conditioned air as part of a heating and air-conditioning system. These units are versatile, supporting multi-position installation, including upflow, downflow, horizontal right, or horizontal left configurations. They are equipped with multi-speed blower motors, allowing for a selection of air volumes to match various applications and desired airflow requirements. The units are compatible with field-installed electric heater kits, available in 5, 7.5, 10, 15, and 20 kW options, which can be added as accessories to provide supplemental heating. The air handlers are designed to work with both AC and heat pump systems, with specific control wiring diagrams provided for each. They feature factory-sealed cabinets, certified to achieve a 2% or less air leakage rate at 1.0 inch water column, contributing to energy efficiency.

Usage Features

The air handlers offer flexible installation options to accommodate different spatial requirements. The default factory configuration is vertical upflow or horizontal right, but units can be field-converted to horizontal left or downflow. For vertical downflow conversion, the indoor coil assembly is removed and reinstalled 180 degrees from its original position. Similarly, for horizontal left conversion, the indoor coil assembly is rotated 180 degrees. Multiple electrical entry locations are provided for convenience during wiring. The units include an integrated filter rack with tool-less door access, simplifying filter maintenance. Condensate drainage is managed by primary and secondary condensate drain fittings, with the drain pan made of polymer with a UVC inhibitor. Horizontal and vertical condensate drain pans are standard, and secondary drain pan kits are recommended for horizontal installations over finished ceilings or living spaces to prevent potential water damage. The unit must be installed in a level position to ensure proper condensation drainage, though a slight rise (up to 1/4 inch) towards the drain is permissible. Proper grounding is essential for safety, and connections for control wiring are made via low voltage pigtails extending from the top of the air handler in an upflow position, or through knockouts on the sides.

Maintenance Features

Ease of maintenance is a key design aspect of the J4AH4P Series Air Handlers. The units feature a dual front panel design, which allows for convenient access to internal components. Both the blower and coil assemblies are designed to easily slide out, facilitating inspection, cleaning, or replacement. The fully-insulated cabinet design helps maintain thermal performance and reduces condensation on the exterior, especially in hot and humid environments. The integrated filter rack with tool-less door access makes filter removal and cleaning straightforward. Filters are not factory-installed and must be added during installation. Regular filter cleaning or replacement is crucial for maintaining optimal airflow and system performance, as reduced airflow can shorten the lifespan of major components. The manual provides instructions for removing and cleaning the air filter, recommending vacuuming or using pure water with a soft brush and mild detergent for heavy dust accumulation. Provisions for disconnecting and cleaning the primary drain line are included, with a recommended 3-inch trap installed as close to the unit as possible to ensure complete drainage and prevent blockages. The design also allows for easy replacement of the piston to a TXV (Thermostatic Expansion Valve), if required for specific system combinations or efficiency ratings. Before any servicing or installation, it is critical to disconnect all power to the unit to prevent electrical shock. The manual emphasizes that maintenance should be performed by trained, qualified service personnel, with consumer service limited to filter cleaning/replacement.