SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of
heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training.
Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.
When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that
are attached to the equipment.
Discharge Air Sensing Kit
Precedent™ Packaged Rooftop Units
Installation Instructions
Model Number: Used With:
FIADAST003* Precedent B cabinet (digit 39 = B) - T/WS*072-120
FIADAST004* Precedent B cabinet (digit 39 = B) - Y/DS*072-120
FIADAST005* Precedent C cabinet (digit 39 = C) - T/WS*150
FIADAST006* Precedent C cabinet (digit 39 = C) - Y/DS*150
FIADAST007* Precedent D cabinet (digit 11 = L, digit 39 = D), T/YS*180-300, T/YH*150-300,
W/D/GS*150-300
FIADAST008* Precedent D cabinet (digit 11 = 0/M/H/B/C/E/G/K/N/P/R, digit 39 = D), T/YS*180-300,
T/YH*150-300, W/D/GS*150-300
Question and Answer IconNeed help?

Do you have a question about the Trane Precedent FIADAST006 Series and is the answer not in the manual?

Summary

Introduction

Warnings, Cautions, and Notices

Defines the three types of safety advisories (WARNING, CAUTION, NOTICE) used in the manual.

Important Environmental Concerns

Discusses chemicals affecting the ozone layer and Trane's advocacy for responsible refrigerant handling.

Important Responsible Refrigerant Practices

Details Trane's commitment to responsible refrigerant practices and technician certification.

Personal Protective Equipment (PPE)

Follow EHS Policies!

Stresses the mandatory adherence to Trane's EHS policies and local regulations for safety.

Copyright

Asserts Trane's ownership of the document and restricts unauthorized reproduction or modification.

Trademarks

Confirms that all referenced trademarks are the property of their respective owners.

General Information

Notes

Contains essential notes about accessory board requirements and the sensing kit's application.

Inspection

Outlines the procedure for inspecting kit components for shipping damage and reporting it.

Parts List

Details the specific parts included for different model numbers (FIADAST003, FIADAST004, etc.).

Installation

Summary

Introduction

Warnings, Cautions, and Notices

Defines the three types of safety advisories (WARNING, CAUTION, NOTICE) used in the manual.

Important Environmental Concerns

Discusses chemicals affecting the ozone layer and Trane's advocacy for responsible refrigerant handling.

Important Responsible Refrigerant Practices

Details Trane's commitment to responsible refrigerant practices and technician certification.

Personal Protective Equipment (PPE)

Follow EHS Policies!

Stresses the mandatory adherence to Trane's EHS policies and local regulations for safety.

Copyright

Asserts Trane's ownership of the document and restricts unauthorized reproduction or modification.

Trademarks

Confirms that all referenced trademarks are the property of their respective owners.

General Information

Notes

Contains essential notes about accessory board requirements and the sensing kit's application.

Inspection

Outlines the procedure for inspecting kit components for shipping damage and reporting it.

Parts List

Details the specific parts included for different model numbers (FIADAST003, FIADAST004, etc.).

Installation

Overview

The Discharge Air Sensing Kit is an accessory designed for Precedent™ Packaged Rooftop Units, specifically to sense the supply air temperature downstream of the fan and/or heat exchanger. This kit is compatible with various Precedent models, identified by their model numbers and cabinet configurations.

Function Description:

The primary function of the Discharge Air Sensing Kit is to accurately measure the temperature of the air being discharged from the unit. This temperature data is crucial for the optimal operation of the HVAC system, allowing for precise control and monitoring of the supply air. The kit includes a temperature sensing module and sensing tubes that are strategically placed within the unit's airflow path. An options board (FIAOPTN002*) must be installed in the unit for this accessory to operate, indicating that it integrates with the unit's control system to provide the temperature readings. Supply air sensing tubes are a standard component on SZVAV, MZVAV, and economizer units, highlighting the importance of this sensing capability in various system configurations.

Important Technical Specifications:

The kit's components vary slightly depending on the specific Precedent unit model and cabinet type it is designed for. Here's a breakdown of the parts included for different configurations:

  • FIADAST003 T/W Models (digit 39 = B):*

    • 1 Temperature sensing module
    • 7 Sensing tubes
    • 3 Mounting brackets
    • 1 Pipe insulation
    • 16 Screws
  • FIADAST004 Y/D Models (digit 39 = B):*

    • 1 Temperature sensing module
    • 5 Sensing tubes
    • 4 Mounting brackets
    • 1 Pipe insulation
    • 16 Screws
  • FIADAST005 T/W Models (digit 39 = C):*

    • 1 Temperature sensing module
    • 6 Sensing tubes
    • 3 Mounting brackets
    • 1 Pipe insulation
    • 12 Screws
  • FIADAST006 Y/D Models (digit 39 = C):*

    • 1 Temperature sensing module
    • 4 Sensing tubes
    • 2 Mounting brackets
    • 1 Pipe insulation
    • 12 Screws
  • FIADAST007/8 (digit 39 = D):*

    • 4 Sensing tubes
    • 1 Temperature sensing module (including Sensor bracket, Harness assembly, Insulation, Wire ties, Sensor bracket screw, and Cap to sensing tube screw connection)
    • 1 Mounting bracket
    • 4 Screws for mounting bracket to fan wall
    • 3 Screws for sampling tube connections

The installation process involves securing the sensing tubes and module within the unit's fan wall or divider, with specific instructions for downflow and horizontal configurations. The system integrates with the Symbio™ 700 UC configuration, which needs to be updated post-installation to enable the feature.

Usage Features:

The Discharge Air Sensing Kit provides continuous monitoring of the supply air temperature, which is critical for maintaining desired indoor environmental conditions. By sensing the temperature downstream of the fan and/or heat exchanger, the system can provide accurate feedback to the unit's control system. This enables the unit to make necessary adjustments to heating, cooling, or fan speed to achieve and maintain the setpoint temperature efficiently. The kit supports both downflow and horizontal airflow configurations, making it versatile for various Precedent unit installations. The integration with the Symbio™ 700 UC controller allows for advanced control strategies and potentially remote monitoring and management of the discharge air temperature.

Maintenance Features:

The manual emphasizes the importance of proper installation and adherence to safety warnings, which indirectly contribute to the longevity and reliability of the device, minimizing the need for frequent maintenance. While specific maintenance procedures for the sensing kit itself are not detailed, the installation instructions highlight several aspects that could be considered maintenance-related or impact future maintenance:

  • Inspection: Before installation, a thorough inspection for shipping damage is required. This proactive step helps ensure that only undamaged components are installed, preventing premature failures.
  • Component Replacement: The kit includes various components like sensing tubes, mounting brackets, and screws, which suggests that individual parts could be replaced if damaged or faulty, rather than requiring a complete kit replacement.
  • Accessibility: The installation process involves removing access panels and duct covers, indicating that these areas are designed for service access, which would facilitate any future inspection, repair, or replacement of the sensing module or tubes. For D cabinet models, the sensor tube hangs from the fan divider wall with service access from both the rear access panel and the supply duct opening, ensuring ease of access for maintenance.
  • Wiring and Insulation: The instructions detail connecting the wire harness and ensuring insulation is properly secured around the temperature sensing module. Proper wiring and insulation are crucial for the sensor's accuracy and protection from environmental factors, reducing the likelihood of electrical issues or sensor degradation over time.
  • System Configuration Updates: After installation, the Symbio™ 700 UC configuration needs to be updated. This digital integration means that software-based diagnostics or calibration might be part of the maintenance routine, ensuring the sensor readings are accurately interpreted by the control system.

Overall, the Discharge Air Sensing Kit is a vital accessory for enhancing the control and efficiency of Precedent Packaged Rooftop Units by providing accurate discharge air temperature data. Its design considers various unit configurations and emphasizes safe and proper installation for reliable operation.