8
PUB. NO. 22-1802-03
Performance
Data
SW7 SW8 0.1 0.3 0.5 0.7 0.9
CFM 583 590 625 622 620
Temp. Rise 50 49 46 46 47
Watts 60 87 126 157 192
CFM 635 687 701 695 694
Temp. Rise 45 42 41 42 42
Watts 69 110 148 183 221
CFM 746 778 803 819 823
Temp. Rise 39 37 36 35 35
Watts 97 140 185 230 272
CFM 779 816 848 866 874
Temp. Rise 57 54 52 51 51
Watts 104 152 201 255 302
CFM 872 939 964 976 985
Temp. Rise 51 47 46 46 45
Watts 136 203 264 312 365
CFM 1069 1102 1102 1110 1078
Temp. Rise 42 40 40 40 41
Watts 227 293 345 403 429
High
Heating
Heating
1st Stage
Heating
2nd
Stage
ON
ON
*UD2B060AFV32A Furnace Heating Airflow (CFM) and Power (watts) vs. External Static Pressure With Filter
Airflow
Setting
Dip Switch Setting External Static Pressure
ON
OFF
OFF
OFF
Low
Medium**
Low
Medium**
High
ON
ON
ON
OFF
OFF
OFF
SW1 SW2 SW3 SW4 0.1 0.3 0.5 0.7 0.9
CFM 517 535 538 546 542
Watts 49 76 105 141 171
CFM 587 594 629 622 618
Watts 61 89 129 159 196
CFM 642 677 705 701 696
Watts 73 109 151 185 222
CFM 676 705 729 736 738
Watts 79 118 159 198 240
CFM 776 814 833 863 867
Watts 103 150 200 251 298
CFM 870 928 961 974 975
Watts 137 198 259 316 361
CFM 831 883 915 935 941
Watts 122 182 238 292 345
CFM 1023 1052 1055 1061 1048
Watts 203 266 316 370 413
CFM 1156 1174 1188 1196 1085
Watts 280 351 415 482 442
CFM 1063 1094 1090 1100 1070
Watts 226 290 344 397 430
CFM 1214 1241 1263 1234 1123
Watts 320 395 476 514 469
CFM 1399 1409 1377 1278 1164
Watts 486 575 604 559 507
Notes:
1. * First letter may be "A" or "T".
2. ** Factory setting.
3. Continuous Fan Setting: Heating or cooling airflow is approximately 50% of selected cooling value.
4. For variable speed low speed airflows are approximately 30% of listed values.
5. LOW 350 cfm/ton is recommended for variable speed application for COMFORT & HUMID CLIMATE setting; NORMAL is 400 cfm/ton;
HIGH 450 cfm/ton is for DRY CLIMATE setting.
OFF
Low (350
CFM/Ton)
ON
OFF
High (450
CFM/ton)
Cooling
*UD2B060AFV32A Furnace Cooling Airflow (CFM) and Power (Watts) vs. External Static Pressure With Filter
Unit
Outdoor
Airflow
Setting
Dip Switch Setting External Static Pressure
1.5
OFF ON
Normal (400
CFM/ton)
ON
ON
OFF
ON
OFF
OFF
ON
OFF
OFF
OFF
ON
ON ON
ON
ONOFFON
ON
OFF
OFF ON
OFF
OFFONON
ON OFF
OFF
OFF
OFF
ON
OFFOFF
OFF
OFF
OFFONOFF
3** OFF OFF
High (450
CFM/ton)
ONOFFOFF
2
Low (350
CFM/Ton)
Normal (400
CFM/ton)
High (450
CFM/ton)
Low (350
CFM/Ton)
Normal (400
CFM/ton)
High (450
CFM/ton)
2.5
Low (350
CFM/Ton)
Normal**
(400