59
2.3 E2: Communication error between indoor and master unit
Digital display output
Description
Communication error between indoor and master unit.
All units stop running.
Error code is only displayed on the master unit.
Trigger / recover condition
Trigger condition: Indoor units and outdoor units cannot communication for 2 minutes after the system power on 20
minutes.
Recover condition: Communication go back to normal.
Reset method: Resume automatically.
Possible causes
Communication wires between indoor and outdoor units not connected properly.
Indoor unit power supply abnormal.
Loosened wiring within electric control box.
Interference from high voltage wires or other sources of electromagnetic radiation.
Communication wire too long.
Damaged main PCB or electric control box communication terminals block.