Troubleshooting
60 RT-SVX26R-EN
1. Open and Lock the unit disconnect switch.
2. Remove the Outside Air Sensor (OAS) from
the
condenser section of unit.
3. Use two (2) wire nuts, to individually
cap the wires.
4. Locate the RTRM (J6). Connect
two (2) wires to
terminals J6-1 and 2.
5. Connect the sensor (OAS) using
two wire nuts to the
two (2) field supplied wires that were connected to
terminals 1 and 2 on J6.
Unit Economizer Control (ECA)
Troubleshooting ReliaTel Control
Verify Economizer Status by Economizer Actuator (ECA)
LED indicator:
OFF: No Power or Failure
ON: Normal, OK to Economize
Slow Flash: Normal, Not OK to Economize
Fast Flash - 1/4 Second On / 2 Seconds Off:
Error Code: Communications Failure
Pulse Flash: 1/30 Second On / 1/4 Second Off: (2
Seco
nds between pulse sequences)
Error Code:
1 Flash: Actuator Fault
2 Flashes: CO
2
Sensor
3 Flashes: RA Humidity Sensor
4 Flashes: RA Temp Sensor
5 Flashes: OA Quality Sensor
6 Flashes: OA Humidity Sensor
7 Flashes: OA Temp Sensor
8 Flashes: MA Temp Sensor
9 Flashes: RAM Fault
10 Flashes: ROM Fault
11 Flashes: EEPROM Fault
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.