Trane ZSENS930AW00MA - Assigning and Unassigning ZSENS930 Sensors; Adding and Assigning a ZSENS930; Unassigning a ZSENS930 Sensor

Trane ZSENS930AW00MA
4 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 1.
ADDING A ZSENS930
FIRST, FOLLOW STEPS ONE THROUGH THREE IN THE INSTALLATION TABLE.
S TE P 4 .1
Access the “Service Menu
STEP 4.2
Put the stat in “Add” mode
STEP 4.3
Add the Z-Wave sensor
STEP 4.4
On screen response
Action
Select
Indoor Sensor Setup
Select “Wireless Sensor
and then on the next
screen select “Add
Stand where the sensor is to be
installed and press and release the
button labeled “INSTALL” on the
interior of the sensor.
Text at top of the screen should change:
From: “
Waiting to Add Device – Press and Hold to Cancel
To: “Adding Device”
Button
To
The STATUS LED will blink rapidly
for 3 seconds
After the sensor is added, “Temperature Sensor added as Device [X]:
Sensor added successfully.” should appear.
Page - 2
Table 2.
ASSIGNING A ZSENS930
FIRST, FOLLOW STEPS 1 THROUGH 3 IN THE INSTALLATION TABLE
ON PAGE 1 AND ALL THE STEPS IN TABLE 1.
S T E P 5.1
Select an
available
sensor
Select the newly added sensor on the right side of the Sensor Assignment screen
under the label “Available Sensors”.
NOTE: The selected sensor will be highlighted in blue.
Screen 1
STEP 5.2
Assign the
sensor
Once the sensor is selected “Assign” will illuminate
on the Navigation Bar. Select “Assign”.
Repeat until all needed sensors are assigned.
STEP 5.3
Sensor
is now
assigned.
The list of assigned and averaged sensors on the left is now updated and the
previously unassigned sensor is now included. (Screen 2)
Screen 2
STEP 5.4 Select “Done” to save and exit the Indoor
Sensor Setup screen.
After this step follow
Step 7 and 8 from Page-1
if not already complete
NOTE: By default all sensors in the Assigned list are
averaged together evenly. Up to four sensors may be used
to define the temperature of the conditioned space.
Table 3.
UNASSIGNING A ZSENS930
STEP 1
Select an
assigned
sensor
Select the sensor to be removed from the assigned sensor list. Use the serial
number to verify the device is the correct sensor.
NOTE: The selected sensor will be highlighted in blue.
Screen 3
STEP 2
Unassign
the sensor
Once an assigned sensor is selected “Assign” will change to
Unassign” on the Navigation Bar.
Select “Unassign”.
STEP 3
Sensor
is now
unassigned.
The list of assigned and averaged sensors is now updated and the previously
asssigned sensor is moved to the “Available Sensors” list. (Screen 4)
NOTE: The order of sensors does not matter. By default the temperature values
from all sensors are averaged together evenly to determine the temperature of
the conditioned space.
Screen 4
STEP 4 Select “Done” to save and exit the
Indoor Sensor Setup screen.
NOTE: The thermostat will not allow you to exit this screen without at least one
sensor assigned to the system.