1
IQ3../.../XNC/... Controller/Interface Installation Instructions TG200911 Issue 1/D 03/09/07
Important: Retain these instructions
Installation Instructions
IQ3.../.../XNC/...
Controller/Interface
CONTENTS
1 Installation - Mounting ....................................................... 1
2 Installation - Configuration ................................................ 4
3 Insertion/Replacement of battery ..................................... 7
4 Disposal ............................................................................. 8
1 Installation - Mounting
Install
1
IQ3xact Installation Instructions TG200766
IQ3xcite Installation Instructions TG200626
Install according to IQ3xact or
IQ3xcite installation instructions
section 3 steps 1 to 11
Connect Serial Interface
2
If /SER/.., serial interface auxiliary board, fitted
or RS232
4 5 6
either 9 way D type plug
or RJ11 socket
If RS485 2 wire
Note that only one of the two RS232 connectors can be used at a time
0V
T
A
T
B
RA
RB
0V
AB
0V
AB
0V
AB
120 ohm
terminator
Terminator switch ON
IQ3../.../SER/XNC/...
either RS485 2 wire, RS485 4 wire, or RS422
2 part connector with 5 screw terminals fo 0.5 to 2.5 mm
2
cross
section area (14 to 20 AWG) cable
If RS485 4 wire
0V
T
A
T
B
RA
RB
0V
TA TB RA
RB
0V
TA TB RA
RB
0V
TA TB RA
RB
120 ohm
terminators
Terminator switch ON
IQ3../.../SER/XNC/...
If RS422
0V
T
A
T
B
RA
RB
TA
TB
RA
RB
0V
Terminator switch OFF
external 100 ohm
terminator
100 ohm
terminator
IQ3../.../SER/XNC/...
32 devices maximum
32 devices maximum
Note pins 1,6,9 - no connection
Note pin 2 - no connection
Note that only one of the RS232 or RS485 connectors can have
a cable connected at any one time in order to comply with Class
B EMC emission standard (EN61000-6-3, residential, commercial,
and light industrial environments).
WARNING: Failure to comply with this requirement will reduce
the unit to Class A (industrial environments); in a domestic
environment the unit may cause radio interference, in which
case the user may be required to take adequate measures.
If the IQ3/XNC/SER controller and its slave units are in the same
cabinet using the same power supply, each device should have
a good physical earth (ground) connection.
Step 2 continued over page