BL67 The Power Supply Concept
Nominal current consumption
The following table informs you on the nominal current consumption I
MB
(5V)
of the various BL67 modules on the module bus, the
resulting nominal current consumption I
MB
(24V)
of the modules via the 24 VDC supply and the nominal current consumption I
I
or I
O
of the
modules via the supply:
Module Nom. current
module bus
I
MB
(5V)
1
)
Gateway PROFIBUS-DP
Gateway DeviceNet™
Gateway CANopen
Gateway Ethernet
BL67-PF-24VDC
BL67-4DI-P
BL67-4DI-N
BL67-4DI-PD
BL67-8DI-P
BL67-8DI-N
BL67-8-DI-PD
BL67-4DO-0.5A-P
BL67-4DO-2A-P
BL67-4DO-2A-N
BL67-8DO-0.5A-P
BL67-8DO-0.5A-N
BL67-16DO-0.1A-P
BL67-4DI4DO-PD
BL67-8XSG-PD
BL67-2AI-V
BL67-2AI-I
BL67-4AI-I/V
BL67-2AI-TC
BL67-2AI-PT
BL67-2AO-I
BL67-2AO-V
BL67-1RS232
BL67-1RS485/422
BL67-1SSI
BL67-1CVI
< 30 mA
< 30 mA
< 30 mA
< 30 mA
< 30 mA
< 30 mA
< 30 mA
< 30 mA
< 30 mA
< 30 mA
< 30 mA
< 30 mA
< 30 mA
< 30 mA
< 30 mA
< 35 mA
< 35 mA
< 35 mA
< 35 mA
< 45 mA
< 40 mA
< 60 mA
< 140 mA
< 60 mA
< 50 mA
< 30 mA
Nom. current
module bus
I
MB
(24V)
2
)
Nom current
input module
I
I
3
)
Nom. current
output module
I
O
4
)
< 150 mA
< 150 mA
< 150 mA
< 150 mA
< 9 mA
< 9 mA
< 9 mA
< 9 mA
< 9 mA
< 9 mA
< 9 mA
< 9 mA
< 9 mA
< 9 mA
< 9 mA
< 9 mA
< 9 mA
< 9 mA
< 9 mA
< 10 mA
< 10 mA
< 10 mA
< 10 mA
< 13 mA
< 12 mA
< 17 mA
< 40 mA
< 17 mA
< 14 mA
< 9 mA
< 100 mA (load current= 0)
< 100 mA (load current= 0)
< 100 mA (load current= 0)
< 100 mA (load current= 0)
< 100 mA (load current= 0)
< 100 mA (load current= 0)
< 100 mA (load current= 0)
< 100 mA (load current= 0)
< 50 mA
< 50 mA
1
) The nominal current consumption via the 5 VDC system supply may not exceed 1.5 A. The primary product of V
MB
(24V)
and I
MB
(24V)
accords to the secondary product of V
MB
(5V)
and I
MB
(5V)
. Power losses have not been considered.
2
) The nominal current consumption via the 24 VDC field supply.
3
) Is limited to 4 A by means of the integrated short-circuit protection.
4
) The nominal current consumption via the field supply: with PROFIBUS-DP it may not exceed 10 A and with DeviceNet™ 8 A.
5
)I
total
= Σ I
MB
(24V)
+ Σ I
I
+Σ I
O
< 40 mA
< 1 mA
< 100 mA
< 40 mA
< 1 mA
< 100 mA
< 12 mA
< 12 mA
< 12 mA
< 30 mA
< 45 mA
< 50 mA
< 25 mA
< 25 mA
< 100 mA
+
I
total
5
)
System supply
General information
The BL67 station is either powered
separately via the PROFIBUS-DP,
CANopen or Ethernet gateway or directly
via the DeviceNet™ or CANopen cable on
the DeviceNet™ gateway.
Power feeding modules can be installed
at any point within the BL67 station. They
provide an isolated field voltage to all
System supply via the
module bus
The number of BL67 modules, which can
be powered via the internal module bus,
depends on the nominal current rating I
MB
of the individual modules on the module
bus. The total current consumption of the
installed BL67 modules may not exceed
1.5 A.
When using the software I/O-ASSISTANT
the menu item <Station - Verify> will
automatically generate an error indication if
the system supply via the module bus is
not reliably ensured.
modules mounted to their right. Power
feeding modules can also be used to
create various potential groups.