26/
1105 Hans Turck GmbH & Co.KG • Witzlebenstraße 7 • D-45472 Mülheim an der Ruhr • Tel. 0208 4952 0 • Fax 0208 4952 264 • www.turck.com
Gateway for BL67 I/O system
Interface for PROFINET IO
BL67-GW-EN-PN
●
3 decimally coded rotary switches
●
Degree of protection IP67
●
LEDs for display of supply voltage,
common alarm and bus errors
●
Interface between BL67 system and
PROFINET IO
●
10/100 Mbps
●
One 4-pole M12 connector,
D coding, for fieldbus connection
●
One 5-pole 7/8" connector for
power connection
Fieldbus
Power supply
Function principle
BL67 gateways are the head component of
a BL67 station. They are designed to inter-
face the modular fieldbus nodes to the hig-
her level fieldbus (PROFIBUS-DP,
DeviceNet™, CANopen, Ethernet).
All BL67 electronic modules communicate
via the internal module bus, whose data are
transferred to the fieldbus via the gateway,
so that all I/O modules can be configured
independently of the bus system.
4
13
2
1 = TD +
2 = RD +
3 = TD
4 = RD
3
4
5
2
1
1 = GND
2 = GND
3 = PE
4 = V
i
5 = V
o
Type BL67-GW-EN-PN
Ident-No. 6827228
Supply voltage 24 VDC
Permissible range 18...30 VDC
Nominal current from module bus 600 mA
Max. field current supply 10 A
Max. system current supply 1.5 A
Transmission rate fieldbus 10/100 Mbps
Fieldbus adressing rotary switch, BOOTP, DHCP, IO-ASSISTANT
Service interface PS/2 socket for I/O-ASSISTANT
Fieldbus connection technology female M12 x 1 connector, 4-pole, D-coded
Power connection technology 5-pole male 7/8" connector
Operating temperature 0...+55 °C
Storage temperature -25...+85 °C
Relative humidity 5 to 95 % (indoor), Level RH-2,
without condensation (storage at 45 °C)
Vibration test according to EN 61131
Shock test according to IEC 68-2-27
Topple and fall according to IEC 68-2-31
and free fall according to IEC 68-2-32
Electromagnetic compatibility according to EN 61131-2
Degree of protection IP67
General technical data see page 21
LED
77,5
145
32
13