3
Compatible base modules
BL67 Electronic modules
8 digital inputs
BL67-8DI-PD
Dimension drawing Type Connection
BL67-B-8M8 Pin configuration
Ident-No. 6827188
8 x M8, 3-pole, female
Comments
Matching connection cable (for example):
SKP3-2-SSP3/S90
Ident-No. 8008685
Wiring diagram
Dimension drawing Type Connection
BL67-B-4M12 Pin configuration
Ident-No. 6827187
4 x M12, 5-pole, female
BL67-B-4M12-P
Ident-No. 6827195
4 x M12, 5-pole, female, paired
Wiring diagram
Comments
If the wire-break detection has been activated,
on the sensor side a jumper between
pin 1 (24 VDC) and pin 2 (diagnostics input)
must be implemented for monitoring of wire-breaks.
Wiring diagram
wire-break detection wiring diagram
3
1
4
v
1 = V
SENS
3 = GND
4 = Input A
3 () BU
1 (+) BN
4 ( ) BK
4
1
3
2
5
v
1 = V
SENS
2 = Input B
3 = GND
4 = Input A
5 = PE
3 () BU
4 ( ) BK
1 (+) BN
2 ( ) WH
5
5
1 (+) BN
3 () BU
2 ( ) WH
4 ( ) BK
5
1 (+) BN
3 () BU
2 ( ) WH
4 ( ) BK