F3200 Installation & Programming Manual Document No: LT0122
Programming
Page 6-34 5 July 2001 Issue 2.7
Item Options Default
AZC Time Delay 1 (Std) 1 Std (2.3 Sec)
2 (AVF/RAD)
3 (SAD)
4 (Delay)
Delay (4) T1 into Alarm 30 Seconds
T2 out of Alarm 0 Seconds
Cct B1 (0-3V) 1 (Inst Alarm) 1 Inst Alarm
2 (Alarm)
3 (Normal)
4 (Fault)
Cct B3 (13-17.5V) 1 (Inst Alarm) 1 Inst alarm (V2.XX
software)
2 (Alarm) For V1.XX software the
3 (Normal) default is Normal (3).
4 (Fault)
Zones Latch/Non Latch Latch
Mapped/Not Mapped Mapped
to MAF/Status Only
Mapped/Not Mapped Mapped
to ANC1, ANC2, BELLS
MAF Brig Relays Operation on Logic Function As Named
Open collector 1-64 Operation on Logic Function Zone 1-64 Non Iso Alarm
Respectively
Variables
Timers Type/Delay No Operation
Module relays 1-64 Configuration and logic Supervision: disabled
equation, Text name Latching: No
Map to MAF: Yes
LED: Yes
Isolatable: Yes
Testable: Yes
Sup Act: Yes
No logic equation
Anc 1 Relay Configuration, logic equation Supervision: disabled
Text name Latching: No
Map to MAF: Yes
Doorholder mode
Isolatable: Yes
Testable: Yes
Sup Act: Yes
No logic equation
Anc 2 Relay Configuration, logic equation, Supervision: disabled
Text name Latching: No
Map to MAF: Yes
Load mode
Isolatable: Yes
Testable: Yes
Sup Act: Yes
No logic equation
TABLE 6.4.1
PROGRAMMABLE PARAMETERS (CONTINUED)
Continued .......