EasyManua.ls Logo

Tyco F3200 - Module Relay Isolate

Tyco F3200
284 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Document No: LT0122 F3200 Installation & Programming Manual
Programming
Issue 2.7 5 July 2001 Page 6-33
Item Options Default
Bells Isol Key (V2.06 or earlier) Enable/Disable Enabled (V2.06 or earlier)
Ancil Isol Key (V2.06 or earlier) Enable/Disable Enabled (V2.06 or earlier)
Keys enable Enable/Disable
All keypad keys for:
Door open/Door closed Door open – all enabled
FF mode/non-FF mode Door closed – all disabled
Remote sounder silence options Enable/Disable sysflt reset, Sysflt reset – enabled
ffcif actions, all commands ffcif actions – enabled
Global network sounder silence Any KeyTX Enabled
Cmd TX Enabled
Receive Enabled
MAF board (NDU only) Present/not present
8 Zone Modules Number Fitted 0-8
8 Relay Modules Number Fitted 0-8
16 LED Display Number Fitted 0-4
Display LEDs Zones/Relays to LEDs 1-1 in order
Alarm Text 1 Smoke 1 Smoke
(Detector Type) 2 Heat
3 FSW (Flowswitch)
4 Manual
5 Valve
6 PSW (Pressure Switch)
7 SPKLR (Sprinkler)
8 & 9 Blank - All Programmable
Inst Alarm Text As per Alarm Text 4 Manual
AZC Mode 1 (Standard) 1 Std
2 (Hi Current)
3 (Lo Current)
4 (Tamper)
5 (Disabled)
TABLE 6.4.1
PROGRAMMABLE PARAMETERS
Continued .......